Plan Review Notes
Plan Review Notes For Permit 05051441
Permit Number 05051441
Review Stop M
Sequence Number 3
Notes
Date Text
2005-10-06 00:00:00*** DENIED ***
 1) RETURN AIR DUCTS NEED TO BE AS LARGE
 AS SUPPLY AIR DUCTS IF GOING BACK TO
 EXIST. A.H.U.. IF GOING TO A TRANSFER
 DUCT RETURN NEEDS TO BE 1 1/2 TIMES
 LARGER THAN SUPPLY AIR DUCTS. PER 2001
 FBC/M 601.4 .
 2) PLEASE SPECIFY RETURN AIR
 APPLAICATION BEING USED.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.