| Notes |
| Date |
Text |
| 2005-06-13 00:00:00 | DENIED:OWNER BUILDER | | | 1.PROVIDE A COMPLETED FORM 600C OR | | | ENERGY AND MANUAL J CALCUALTIONS FOR THE | | | ADDITION PER 2001 FBC CHAPTER 13 SUB | | | CHAPTER 6. | | | | | | 2.RETURN AIR REQUIRED FROM FLORDIA | | | ROOM AND THE "NEW ROOM".RETURN AIR | | | SHALL BE SIZED IN ACCORDANCE WITH 2001 | | | FBC(M)601.4.INDICATE DUCT & GRILLE | | | SIZE ON THE PLAN. | | | | | | 3.BATHROOM SHALL HAVE A WINDOW WITH A | | | CLEAR OPENING OF 3 SQUARE FEET OR HAVE | | | MECHANICAL VENTILATION PER 2001 FBC(M) | | | 402.3.1. | | | | | | 4.PROVIDE EQUIPMENT SCHEDULE FOR THE | | | EXISITNG A/C. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|