Plan Review Notes
Plan Review Notes For Permit 05051441
Permit Number 05051441
Review Stop M
Sequence Number 1
Notes
Date Text
2005-06-13 00:00:00DENIED:OWNER BUILDER
 1.PROVIDE A COMPLETED FORM 600C OR
 ENERGY AND MANUAL J CALCUALTIONS FOR THE
 ADDITION PER 2001 FBC CHAPTER 13 SUB
 CHAPTER 6.
  
 2.RETURN AIR REQUIRED FROM FLORDIA
 ROOM AND THE "NEW ROOM".RETURN AIR
 SHALL BE SIZED IN ACCORDANCE WITH 2001
 FBC(M)601.4.INDICATE DUCT & GRILLE
 SIZE ON THE PLAN.
  
 3.BATHROOM SHALL HAVE A WINDOW WITH A
 CLEAR OPENING OF 3 SQUARE FEET OR HAVE
 MECHANICAL VENTILATION PER 2001 FBC(M)
 402.3.1.
  
 4.PROVIDE EQUIPMENT SCHEDULE FOR THE
 EXISITNG A/C.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.