| Notes |
| Date |
Text |
| 2005-06-02 00:00:00 | | | | PLEASE PROVIDE A SITE/FLOOR PLAN SHOWING | | | THE PHYSICAL LOCATION OF THE SERVICE AND | | | GENERATOR EQUIPMENT SO THAT DISCONNECT | | | GROUPING AND COMPLIANCE WITH 225.31 & 32 | | | CAN BE VERIFIED. | | | ALSO PLEASE SUBMIT A LOAD CALCULATION | | | FOR THE PANEL/CIRCUITS BEING FED FROM | | | THE GENERATOR TO VERIFY COMPLIANCE WITH | | | 702.5. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|