| 2005-06-09 00:00:00 | ************ UNSAT ************* |
| | |
| | **PLANS SUBMITTED FOR "PLAN REVIEW" |
| | ONLY. |
| | PLANS HAVE NOT BEEN SUBMITTED FOR PERMIT |
| | APPLICATION. |
| | |
| | 1)NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITEL BLOCKS. PLEASE SEE FAC |
| | 61G15-23.002, FS 471.023 |
| | |
| | 2)NOTE: PLEASE SEE FS 471.025, PLANS ARE |
| | REQUIRED TO BE SIGNED , DATED AND SEALED |
| | BY SAID ENGINEER OF RECORD. |
| | |
| | 3)NOTE: PLEASE SEE FBC 104.2.1, ALL |
| | PLANSMUST CONTAIN THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLEFOR |
| | PLANS/DESIGN. |
| | PLEASE SEE THIS IS REQUIRED FOR ALL |
| | PLANS WHEATHER OR NOT COMMENT IS MADE BY |
| | OTHER REVIEWER(S). |
| | |
| | 4)NOTE: PLEASE SEE NOTE #9 ON E-5 |
| | MENTIONS, TO DEMO LPR AND REPLACE, |
| | HOWEVER RISER AND PLANS DO NOT SHOW/NOTE |
| | THIS AND BEING REPLACED OR NEW. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE SEE MIN CLEARENCE |
| | REQUIREMENTS PER 110.26 |
| | PLEASE SEE IF PANEL EXISTING DO NOT MEET |
| | MIN CLEARENCE, NEW PANELS MAY NOT BE |
| | INSTALLED IN SMAE LOCATION WITHOUT |
| | MEETING MIN CLEARENCE REQUIREMENTS. |
| | PLEASE ALSO SEE WALL BEING SHOWN |
| | DIRECTLY IN THE MIDDLE OF AN ELECTRICAL |
| | PANEL. |
| | PLEASE SEE ELECTRICAL PANEL DISCRIPTION |
| | MENTIONS PANEL LPS TO BE IN SHOWER AREA? |
| | PLEASE CLARIFY THIS. ELECTRICAL PANEL |
| | CONTAINING OCP SAHLL NOT BE INSTALL IN |
| | SHOWERS. |
| | PLEASE ALSO SEE NEW PANEL LPW. |
| | |
| | 6)NOTE: PLEASE INDICATE ALL CIRCUITING |
| | ON PLANS AND CORRELATE WITH THE |
| | SUBMITTED PANEL SCHEDULES. |
| | 215.5 |
| | |
| | |
| | 7)NOTE: PLEASE VERIFY OCP FOR NEW 80 GAL |
| | WH. THIS IS ONLY A NOTE TO VERIFY. |
| | |
| | 8)NOTE: PLEASE SEE RISER DIAGRAM NOTE |
| | MENTIONS A 24HR AMP READING. PLEASE SEE |
| | 220.35 FOR MIN REQUIREMENTS FOR EXISTING |
| | LOADS WHEN LOAD CALCULATIONS ARE NOT |
| | PERFORMED. |
| | PLEASE INCLUDE LOAD CALCAULTIONS THROUGH |
| | MDP FOR NEW ADDED LOADS. |
| | |
| | 9)NOTE: PLEASE SEE RISER DIAGRAMS ARE |
| | NOTED AS BEING EXISTING. SOME DETAILS IN |
| | EACH RISER SHOWN NOTES ITEMS AS NEW AND |
| | SOME ARE NOTED AS EXISTING, SOME DO NOT |
| | CONTAIN ANY INFORMATION AS NEW OR |
| | EXISTING.??? |
| | 215.5 |
| | |
| | 10)NOTE: PLEASE CORRELATE NOTES AND |
| | PANELS ON RISER. SEE LPLM, ?LPM? |
| | PLEASE SEE NOTES WHICH MENTIOSN THAT |
| | EXISTING BRKRS DO NOT WORK, YET PLANS DO |
| | NOT SHOW NEW BRKRS ETC.?? |
| | 215.5 |
| | |
| | 11)NOTE: PLEASE VERIFY AND SHOW METHOD |
| | OF EQUIPMENT GORUNDING BETWEEN SOME |
| | PANELS WHERE NO EQUIPMENT GROUNDING |
| | CONDUCTORS ARE SHOWN. |
| | 215.5,250.110,.250.122 ETC. |
| | |
| | PLEASE COMPLETE PLANS AND SUBMIT THE |
| | ABOVE INFORMATION FOR REVIEW. IF THERE |
| | ARE ANYQUESTIONS, PLEASE CALL. |
| | |