| Plan Review Notes For Permit 05051368 |
| Permit Number |
05051368 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-03-16 00:00:00 | *********** UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE RISER STILL SHOWS AN | | | "EQUIPMENT GROUNDING CONDUCTOR" FROM | | | METER TO THE FIRST MEANS OF DISCONNECT. | | | PLEASE SEE THIS WAS NOTED ON FIRST TWO | | | REVIEWS, AND REDLINED ON LAST REVIEW TO | | | ISSUE PERMIT. THIS HAS STILL NOT BEEN | | | CORRECTED. PLEASE SEE PLANS INDICATE 5 | | | CONDUCTORS FROM METER. | | | PLEASE KNOW, IF PLANS COME BACK WITH | | | SAME COMMENT NOT ADDRESSED THIS OFFICE | | | WILL HAVE NOT CHOICE BUT TO ISSUE A 4X | | | FEE FOR THE PLAN REVIEW PORTION OF THE | | | PERMIT FEE AS REQUIRED PER FS | | | 553.80(2)(B). | | | | | | 2)NOTE: PLEASE SEE WIND LOADS AND | | | CALCULATIONS SHALL BE SHOWN FOR LIGHT | | | POLES TO MEET FBC 140MPH. THIS WAS ALSO | | | REDLINED, HOWEVER PLANS DO NOTY REFLECT | | | THIS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|