Plan Review Notes
Plan Review Notes For Permit 05051368
Permit Number 05051368
Review Stop E
Sequence Number 5
Notes
Date Text
2006-03-16 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SEE RISER STILL SHOWS AN
 "EQUIPMENT GROUNDING CONDUCTOR" FROM
 METER TO THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE THIS WAS NOTED ON FIRST TWO
 REVIEWS, AND REDLINED ON LAST REVIEW TO
 ISSUE PERMIT. THIS HAS STILL NOT BEEN
 CORRECTED. PLEASE SEE PLANS INDICATE 5
 CONDUCTORS FROM METER.
 PLEASE KNOW, IF PLANS COME BACK WITH
 SAME COMMENT NOT ADDRESSED THIS OFFICE
 WILL HAVE NOT CHOICE BUT TO ISSUE A 4X
 FEE FOR THE PLAN REVIEW PORTION OF THE
 PERMIT FEE AS REQUIRED PER FS
 553.80(2)(B).
  
 2)NOTE: PLEASE SEE WIND LOADS AND
 CALCULATIONS SHALL BE SHOWN FOR LIGHT
 POLES TO MEET FBC 140MPH. THIS WAS ALSO
 REDLINED, HOWEVER PLANS DO NOTY REFLECT
 THIS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  