| 2005-07-26 00:00:00 | *********** UNSAT 2ND REVIEW ********** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND ONE NEW NOTE. |
| | |
| | 1)NOTE: PLEASE SEE LETTER FROM |
| | CONTRACTOR FOR CHNAGE IN SCOPE OF WORK |
| | IS STILL REQUIRED TO BE CORRECTLY |
| | NOTORIZED PER FS 117 WITH ALL |
| | INFORMATION SET UP AS SET-FORTH IN FS |
| | ABOVE. |
| | |
| | 2)NOTE: PLEASE SEE RISER DIAGRMA HAS NOW |
| | BEEN CHANGED TO INCREASE MAIN TO 125A'S, |
| | HOWEVER METER IS STILL SHOWN AS 100A'S. |
| | OLD MAIN WAS 100A'S |
| | PLEASE CORRELATE. |
| | 215.5,240.4,310.16 ETC. |
| | |
| | 3)NOTE: PLEASE SEE EQUIPMENT GROUNDING |
| | CONDUCTOR FROMM METER TO MAIN/FIRST |
| | MEANS OF DISCONNECT. PLEASE SEE 250.6, |
| | 250.24, AN "EQUIPMENT GROUNDING |
| | CONDUCTOR" IS ONLY INSTALLED AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | |
| | 4)NOTE: PLEASE SEE CA NUMBER WHICH |
| | APPEARS TO BE ON TITLE BLOCK WHICH NOT |
| | NOT VISABLE. |
| | PLEASE INCREASE FONT IN CAD OR ? TO MAKE |
| | THIS READABLE. |
| | |
| | 5)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) ATTACHED WITH RESPECT TO |
| | DESIGN PROFESSIONAL AND PLANS WITH |
| | REPEAT COMMENTS. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |