| Date |
Text |
| 2005-06-08 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE WIRING RISER SHOWS A |
| | NEW ELECTRICAL PANEL BEING INSTALLED , |
| | HOWEVER NO INFORMATION IS SHOWN FOR |
| | FEEDERS, OCP, CONDUIT ETC. |
| | |
| | 2)NOTE: PLEASE SEE ALL CONTINOUS LOADS |
| | ARE TO BE SHOWN AT 125%.; PLEASE SEE |
| | POOL MOTOR, HEAT PUMP ETC. |
| | 3 OR MORE HRS. |
| | 215.3,230.42,680.9 |
| | |
| | 3)NOTE: PLEASE SEE BLDG REVIEW COMMENTS. |
| | VALUATION SHALL BE BASED ON ON LABOR AND |
| | MATERIALS EVEN IF OWNER SUPPLIED. |
| | PLEASE SEE PERMIT APPLICATION HAS |
| | $12,794 FOR VALUE. THIS VALUE MAYBE |
| | ADJUSTED IN-HOUSE IF NOT INCREASED. |
| | |
| | 4)NOTE:PLEASE SEE PLANS APPEAR TO BE |
| | SIGNED WITH INITIALS. IF INDEEDTHIS IS |
| | THE LEGAL SIGNATURE FOR ENGINEER.PLEASE |
| | HAVE ENGINEER PROVIDE A SIGNED, SEALED, |
| | DATED AND NOTORIZED LETTER. THIS LTR |
| | MUST STATE THIS IS THE LEGAL SIGNATURE |
| | OF SAID ENGINEER. |
| | |
| | 5)NOTE: PLEASE SUBMIT MANUFACTURE SPEC |
| | SHEETS FOR HEAT PUMP PROPOSED SHWOING |
| | THE LISTING FROM A NRTL. |
| | THE SPECS DO NOT SHOW THIS.110.3 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |