| Plan Review Notes For Permit 05051311 |
| Permit Number |
05051311 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-10-17 13:53:28 | REVISION TO MECHANICAL PLAN PAGE M-2. | | | *** DENIED *** | | | 1) PLEASE ALSO SUBMIT PAGE M-1 AS THIS PAGE NEVER | | | PASSED A MECHANICAL REVIEW. | | | | | | 2) IT WOULD BE ADVISABLE TO REVISE YOUR ENERGY | | | CALCULATIONS ALSO AS THE ONE ON FILE IS CALLING FOR | | | 15.50 SEER A/C SYSTEMS AND YOUR PLANS PAGE M-2SYSTEM | | | #2 IS ONLY 15.00 SEER. | | | | | | 3) ALSO YOU SHOULD REVISE YOUR MANUAL J CALCULATION AS | | | THE PLANS ARE CALLING FOR MORE SENSIBLE BTU'S THAN THE | | | MANUAL J CAL' S ON FILE WILL PERMIT. | | | | | | 4) SEE PAGE M-2 MASTER BEDROOM, NEED TO PROVIDE RETURN | | | AIR, PER 2001 FBC/M 601.4 . | | | | | | 5) SEE PAGE M-2 AHU #4, RETURN AIR GRILL IS NOT SIZED, | | | PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|