| Plan Review Notes For Permit 05051300 |
| Permit Number |
05051300 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-09-03 00:00:00 | **********UNSAT ********* | | | | | | | | | 1)NOTE: PLEASE VERIFY SEC'S IN EXISTING | | | RISER FOR 200A SERVICE SHOWN. | | | 240.4,310.16 | | | | | | 2)NOTE: PLEASE SEE PREVIOUS REDLINED | | | NOTE FOR 700.12E. | | | THIS WAS NOT CORRECTED FOR REVSIONS. | | | THE BRANCH CIRCUIT FEEDING THE UNIT | | | EQUIPMENT SHALL BE THE SAME BRANCH | | | CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD | | | OF ANY LOCAL SWITCHES. | | | | | | 3)NOTE: PLEASE VERIFY 2/0'S SHOWN FOR | | | 100A PANELS. PLEASE ALSO VERIFY MCB'S | | | SHOWN FOR BOTH INSIDE PANELS?? | | | PLEASE NOTE: EITHER ABOVE DOES NOT | | | VIOLATE NEC, HOWEVER IF SHOWN THIS WAY, | | | THEN 2/0'S AND MCB'S IN INTERIOR PANELS | | | WILL BE REQUIRED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|