Plan Review Notes For Permit 05051300
Permit Number 05051300
Review Stop E
Sequence Number 4
Notes
Date Text
2005-09-03 00:00:00**********UNSAT *********
  
  
 1)NOTE: PLEASE VERIFY SEC'S IN EXISTING
 RISER FOR 200A SERVICE SHOWN.
 240.4,310.16
  
 2)NOTE: PLEASE SEE PREVIOUS REDLINED
 NOTE FOR 700.12E.
 THIS WAS NOT CORRECTED FOR REVSIONS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 3)NOTE: PLEASE VERIFY 2/0'S SHOWN FOR
 100A PANELS. PLEASE ALSO VERIFY MCB'S
 SHOWN FOR BOTH INSIDE PANELS??
 PLEASE NOTE: EITHER ABOVE DOES NOT
 VIOLATE NEC, HOWEVER IF SHOWN THIS WAY,
 THEN 2/0'S AND MCB'S IN INTERIOR PANELS
 WILL BE REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  