| Plan Review Notes For Permit 05051300 |
| Permit Number |
05051300 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-08-11 00:00:00 | ****** PLANS REDLINED.******* | | | | | | PREVIOUS REVIEWS MENTIONED ALL EM/ EXT | | | LTS TO BE WIRED AHEAD OF ALL LOCAL | | | BRANCH CIRCUIT FEEDING LIGHTING IN THOSE | | | AREAS. | | | PLEASE SEE PLANS CONTAIN A NOTE FOR | | | THIS, HOWEVER PLANS FOR BOTH TENANT | | | SPACES INDICATE EACH OF THESE PANELS | | | PROVIDING A DEDICATE CIRCUIT FOR EACH | | | AND NOT ON LOCAL BRANCH CIRCUIT????? | | | | | | PLEASE SEE THIS IS TO BE REVISED LONG | | | WITH ANY OTHER CHANGES BEFORE ANY ROUGH | | | ELECTRICAL INSPECTION. | | | | | | PLEASE CALL IF THERE ARE ANY QUESTIONS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | NOC EXPIRED FS 713.13(2) | | | PLEASE SEE IF WORK HAS NO TCOMMENCED | | | WITH IN 90 DAYS OF RECORDING,NOC EXPIRES | | | AND MUST BE RE-RECORDED. |
|