| Plan Review Notes For Permit 05051300 |
| Permit Number |
05051300 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-14 00:00:00 | ****DENIED**** | | | | | | 1) THE DRAWINGS SHOW SMOKE ALARMS WITH | | | STROBES. IS THERE A FIRE ALARM SYSTEM OR | | | ARE THE SMOKE ALARMS TIED INTO DUCT | | | SMOKE DETECTORS? | | | | | | 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED TO BE MOUNTED AT LOCATIONS NOT | | | TO EXCEED 75' TRAVEL DISTANCE. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR THE FIRE ALARM AND FIRE | | | SPRINKLER REMODEL IF APPLICABLE. | | | | | | 4) PLEASE INDICATE THE FIRE RATED DOORS | | | IN TERMS OF HOURS OR MINUTES. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 805-6722 OR 835-2951 |
|