| Date |
Text |
| 2005-06-14 00:00:00 | *********** UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE PLANS APPEAR TO SHOW |
| | TO SEPARATE TENANTS SHARING THE SAME |
| | SPACE? |
| | PLANS CALL FOR BUS> "A" AND BUS>"B"?? |
| | PLEASE SEE FIRE AND BLDG COMMENTS. |
| | PLEASE SEE PLANS INDICATE A 1HR TENANT |
| | SEPARATION. |
| | PLEASE SEE CIRCUITING FOR TWO SEPARATE |
| | TENANTS SHALL BE SEPARATED. PLEASE SEE |
| | THAT ELECTRICLA PANEL FOR CIRCUITING IN |
| | ONE BUSINESS CAN NOT BE LOCATED IN |
| | ANOTHERS TENANT SPACE.210.25 |
| | |
| | 2)NOTE: PLEASE CLARIFY FRONT WINDOW IS |
| | INDICATED ON PLANS AS "STOREFRONT |
| | WINDOW"? PLEASE SEE IF OCCUPANCY IS |
| | GOING TO BE MERCHANTILE OF ANY KIND, |
| | "SHOW WINDOW RECEPTS ABOVE WINDOW WILL |
| | BE REQUIRED. |
| | 210.62 |
| | |
| | 3)NOTE: PLEASE SEE 700.12E FIR |
| | CIRCUITING OF EM/EXT LTS.THE BRANCH |
| | CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA |
| | AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | |
| | 4)NOTE: PLEASE INDICATE NEW OR EXISTING |
| | REQUIRED SIGN CIRCUIT(S). |
| | 600.5 |
| | |
| | PLEASE SEE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OL/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABVOE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |