Plan Review Notes
Plan Review Notes For Permit 05051287
Permit Number 05051287
Review Stop E
Sequence Number 2
Notes
Date Text
2005-11-17 00:00:00******* UNSAT **********
  
 1)NOTE: PLEASE SUBMIT TWO(2) COMPLETE
 SETS OF SIGNED, DATED AND SEALED PLANS.
 PLEASE SEE ONE SET OF CIVIL PLANS ARE
 SEALED PHOTOCOPIES.
 PLEASE SEE FS 471.025, WHICH REQUIRES AN
 "ORIGINAL" SIGNATURE FROM THE ENGINEER.
 PLEASE ALSO SEE ONLY ONE SET OF
 ELECTRICAL PLANS WERE SUBMITTED.
  
 2)NOTE: PLANS REDLINED FOR MISSING
 EQUIPMENT GROUNDING CONDUCTOR FROM MCB
 TO SUB PANEL.
 250.110,25.24,250.122
  
 *** PLEASE KNOW, ALL OF THE ABOVE IS
 REQUIRED WHETHER OR NOT COMMENTS ARE NOT
 MADE BY OTHER REVIEWER(S).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]