| Date |
Text |
| 2005-06-17 00:00:00 | ************ UNSAT***************** |
| | |
| | 1)NOTE: PLEASE SEE FS 481.221, 471.025, |
| | WHICH REQUIRED SHEETS TO BE SIGNED,DATED |
| | AND SEALED BY THE ARCH/ENG OF RECORD. |
| | PLEASE ALSO SEE FBC 104.2.1 WHICH |
| | REQUIRES THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR PLANS AND |
| | DESIGN. |
| | PLEASE SEE OTHER SHEETS APPEAR TO BE |
| | "SIGNED" WITH INITIALS. IF THIS INDEED |
| | THE LEGAL SIGNATURE OF DESIGN |
| | PROFESSIONAL, PLEASE PROVIDE ASIGNED, |
| | DATED AND SEALED LTR NOTORIZED UNDER FS |
| | 117 FOR LEGAL SIGNATURE VERIFICATION. |
| | THIS WILL BE PLACE IN SIGNATURE FILE FOR |
| | FUTURE REFERENCE. |
| | |
| | 2)NOTE: PLEASE COMPLETE RISER DIAGRMA |
| | WITH ALL CONDUCTORS AS REQUIRED UNDER |
| | 215.5,310.16,240.4 ETC. |
| | SEC'S, FEEDERS ETC. |
| | |
| | 3)NOTE: PLEASE SUBMIT PANEL SCHEDULES TO |
| | CORRELATE WITH CIRCUITING ON PLANS. |
| | PLEASE BE SURE ALL INFORMATION IS SHOWN |
| | ON PANEL SCHEDULES. |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | AS REQUIRED PER 220, 215.5 |
| | |
| | 5)NOTE: PLEASE SHOW ALL LOCATIONS OF |
| | SERVICE EQUIPMENT. |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SEE 250.50 FOR MIN |
| | GROUNDING ELECTRODE SYSTEM CONNECTIONS. |
| | PLEASE SEE RISER ONLY MENTIONS FOOTER |
| | STEEL. |
| | PLEASE SEE FBC 104.2.1, CODE SHALL NOT |
| | BE REFERENCED IN WHOLE OR IN PART FOR |
| | TECHNICAL CODES. |
| | |
| | 7)NOTE: PLEASE SEE PLANS MENTIONS LT |
| | POLES, IF LT POLESE ARE GOING TO BE |
| | INSTALLED, PLANS ARE REQUIRED TO SHOW |
| | POLES, SHOW WIND LOAD PER FBC 140MPH AND |
| | SUBMIT WIND LOAD CALCS AT THIS TIME FOR |
| | REVIEW. |
| | |
| | PLEASE SEE DUE TO PLANS NOT BEING |
| | COMPLETE ARE THIS TIME, A COMPLETE |
| | REVIEW CAN NOT BE DONE. |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. ONE SET OF OLD SHEETS SHALL BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE BE SURE TO SEE ANY COMMENTS FROM |
| | OTHER REVIEW(S) WHICH MAY HAVE AN AFFECT |
| | ON ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| 2005-06-15 00:00:00 | IN ELEC FOR REVIEW. |