Plan Review Notes
Plan Review Notes For Permit 05051287
Permit Number 05051287
Review Stop B
Sequence Number 1
Notes
Date Text
2005-06-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051287
 ADD: 1122 P. B. LAKES
 CONT:CSR HEAVY CONSTTRUCTION
 TEL: (954)650-6733
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL. S. S. 481.221,/ 471.025 WHICH
 SHEETS TO BE SIGNED AND SEALED BY ARCH/
 ENG OF RECORD. ALSO SEE 104.2.1* WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS &
 DESIGN.
  
 3) SHEET A-1/ A-2 WRONG BASIC WIND
 VELOCITY:FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO BE DISIGNED TO THIS WIND SPEED.
  
 4) SHEET A-1, ROOF DEAD LOAD 2 PSF,
 2002.4DESIGN. STRUCTURAL MEMBERS
 SUPPORTING SCREEN ENCLOSURES SHALL BE
 DESIGNED TO SUPPORT MINIMUM WIND LOADS
 GIVEN IN TABLE 2002.4.WHERE ANY
 VALUE IS LESS THAN 10 PSF (479 PA) USE
 10 PSF.
  
 1606.1.2 MINIMUM WIND LOADS. THE WIND
 LOADS USED IN THE DESIGN OF THE
 MAIN WIND-FORCE-RESISTING SYSTEM SHALL
 NOT BE LESS THAN 10 POUNDS PER
 SQUARE FOOT (0.479 KN/M^2) MULTIPLIED
 BY THE AREA OF THE BUILDING OR
 STRUCTURE PROJECTED ON A VERTICAL
 PLANE NORMAL TO THE WIND DIRECTION.IN
 THE CALCULATION OF DESIGN WIND LOADS
 FOR COMPONENTS AND CLADDING FOR
 BUILDINGS, THE ALGEBRAIC SUM OF THE
 PRESSURES ACTING ON OPPOSITE FACES
 SHALL BE TAKEN INTO ACCOUNT.THE
 DESIGN PRESSURE FOR COMPONENTS AND
 CLADDING OF BUILDINGS SHALL NOT BE
 LESS THAN 10 POUNDS PER SQUARE FOOT
 (0.479 KN/M^2) ACTING IN EITHER
 DIRECTION NORMAL TO THE SURFACE.THE
 DESIGN FORCE FOR OPEN BUILDINGS AND
 OTHER STRUCTURES SHALL NOT BE LESS
 THAN 10 POUNDS PER SQUARE FOOT (0.479
 KN/M^2) MULTIPLIED BY THE AREA
 A_F.
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A6-8 PROVIDE ROOF/ WALL DETAILS BUT NO
 INFORMATION AS TO ENGINEERED DRAWINGS
 FROM THE MANUFACTURER FOR SPANS OF BEAMS
 OR COLUMNS OR ROOF PANEL SPANS?
  
 6) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
  
 7)4 INDICATE THE USE OF ELASTOMARIC
 STUCCO ? IS THIS EFIS SYSTEMS?
  
 8) A-1 INDICATES SHEAR WALL CONSTRUCTION
  
 PROVIDE INFORMATION AS TO WHICH WALLS
 ARE THE SHEAR WALLS.
  
 9) A-2 VARIOUS FOUNDATION DETAILS
 INDICATE THE OVER-ALL HEIGHT OF THE
 FOUNDATION 12" TALL, SEE 1804.1.3 THE
 BOTTOM OF THE FOUNDATION SHALL EXTEND NO
 LESS THAN 12" BELOW FINISH GRADE.
  
 10) SHEET A-5,FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS HAVE VARIOUS ABBREVIATIONS?
  
 11) SHEET A-7 DETAIL A3 INDICATES THE
 USE OF A DOUBLE BEAM BUT THE PLANS
 INDICATE NO FASTENING BETWEEN BEAMS TO
 CREATE A SINGLE MEMBER? PROVIDE TABLE
 FOR SPANS.
  
 12)SHEETA6INDICATES A DETAIL B7 ON SHEET
 A8, DETAIL IS MISSING.
  
 13)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-10 INDICATES THE USE OF 2"X2"
 ALUM ANGLE BRACES, WHY DO THEY STOP
 SHORT OF THE RIGHT END OF THE BUILDING.
  
 14) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR SWING DOORS
 B) ROOF ASSEMBLIES
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 15) 1707.4.3 EACH EXTERIOR DOOR ASSEMBLY
 NOT COVERED BY 1707.4.2 (GLAZED DOORS)
 SHALL BE LISTED AND TEST- ED FOR A
 PERIOD EQUAL TO THE QUANITY 3600/ V
 WHERE THE TIME PERIOD IS IN SECTIONS AND
 V IS IN MILES PER HR TAKEN FROM FIGURE
 1606. THE TIME PERIOD SHALL ALSO INCLUDE
 A 10 SECOND PERIOD AT A LOAD EQUAL TO
 1.5 TIMES THE DESIGN PRESSURE. DADE
 COUNTY & SBCCI REPORTS ARE ACCEPTED.
  
 16)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026