Plan Review Notes
Plan Review Notes For Permit 05051268
Permit Number 05051268
Review Stop B
Sequence Number 1
Notes
Date Text
2005-07-18 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO COMPLETE SETS OF PLANS.
  
 4) SUBMIT TWO COPIES OF A SURVEY
 INDICATING THE LOCATION OF THE ADDITION
 AND DISTANCE TO PROPERTY LINES.
  
 5) THE ORIGINAL WET SIGNATURE OF THE
 ENGINEER IS REQUIRED ON THE PLANS.
 SIGNATURE STAMPS ARE NOT ACCEPTABLE. SEE
 FAC 61G15-23.002.
  
 6) SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR WINDOWS, DOORS, GLASS
 BLOCK, ROOFING MATERIAL, STORM PANELS
 AND HURRICANE ANCHORS. PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER
 OCTOBER 1, 2003 ARE REQUIRED TO COMPLY
 WITH THE FLORIDA PRODUCT APPROVAL
 SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 7) SUBMIT TWO COPIES OF ENERGY CALCS.
 SIGNED BY OWNER/AGENT. THE INSULATION OF
 THE EXTERIOR MASONRY WALLS IS REQUIRED
 TO HAVE AN VALUE OF R-5. SEE TABLE 6B-1
 WHICH REQUIRES ALL "TO BE INSTALLED"
 VALUES TO BE EQUAL TO OR MORE EFFICIENT
 THAN THE REQUIRED LEVELS.
  
 8) UNDER DESIGN PARAMETERS ON SHEET 1
 REVISE MINIMUM ROOF HEIGHT TO MEAN ROOF
 HEIGHT.
  
 9) THE TOTAL ROOF DEAD LOAD HAS BEEN
 LEFT BLANK ON SHEET 1.
  
 10) SPECIFY THE TRUSS BOTTOM CORD LIVE
 LOAD. SEE FBC TABLE 1604.1.
  
 11) ON SHEET 1 REVISE INTERIOR PRESSURE
 COEFFICIENT TO INTERNAL PRESSURE
 COEFFICIENT AND ADD PLUS AND MINUS SIGNS
 TO INDICATE POSITIVE AND NEGATIVE
 PRESSURES. SEE ASCE 7-98 TABLE 6-7.
  
 12) REVISE THE ROOF SHEATHING FASTENER
 SPACING TO COMPLY WITH CITY OF WPB
 AMENDMENTS TO FBC TABLE 2306.1, WHICH
 REQUIRES 4" OC AT THE EDGES AND 6" OC IN
 THE FIELD IN ZONE 3.
  
 13) SPECIFY THE LOCATION AND SIZE OF THE
 ATTIC ACCESS ON THE PLANS. SEE FBC
 2309.6.
  
 14) SPECIFY THE SIZE OF THE SOFFIT
 SCREEN VENTS ON SHEET 6. SEE FBC
 2309.7.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  