2005-05-30 00:00:00PROVISO:
 PER 2001 FBC/M 601.4 EXCEPTION #2 & 3,
 TRANSFER GRILLES SHALL BE A MINIMUM OF
 50 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM OF SUPPLY AIR FOR THROUGH THE WALL
 TRANSFER GRILLES.ALL SUPPLY AIR INTO
 THE MASTER SUITE SHALL BE INCLUDED FOR
 PROPER SIZING OF THE RETURN AIR.
  