| Plan Review Notes For Permit 05051254 |
| Permit Number |
05051254 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-30 00:00:00 | PROVISO: | | | PER 2001 FBC/M 601.4 EXCEPTION #2 & 3, | | | TRANSFER GRILLES SHALL BE A MINIMUM OF | | | 50 SQUARE INCHES (OF GRILLE AREA) TO 100 | | | CFM OF SUPPLY AIR FOR THROUGH THE WALL | | | TRANSFER GRILLES.ALL SUPPLY AIR INTO | | | THE MASTER SUITE SHALL BE INCLUDED FOR | | | PROPER SIZING OF THE RETURN AIR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|