Plan Review Notes
Plan Review Notes For Permit 05051245
Permit Number 05051245
Review Stop P
Sequence Number 1
Notes
Date Text
2005-06-18 00:00:00PLUMBING PLAN REVIEW DENIED FBC 2001
 (1) SHT P-1 ISOMETRIC ,SANITARY RISER
 SHOWS A DIRECT CONNECTION TO DWV SYSTEM,
 WITHOUT WASTE PUMP.
 (2)PROVIDE MANFACTURE CUT SHEETS ON
 WASTE PUMP.
 (3)SHT A-1 BREAK ROOM SINK:
 SEC 11-4.24.4 MAX DEPTH 6-1/2"
 (4)COMPLY WITH ELECTRIC PLAN REVIEW,
 NOTE #1,#2
 END OF COMMENTS