| 2005-06-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1. NO PERMIT PERTAINING TO A GENERATOR |
| | SHALL BE ISSUED UNTIL AN APPLICATION FOR |
| | THE GENERATOR, (RES-GEN), WITH A REVIEW |
| | FOR THE GENERATOR BY BUILDING, ELECTRIC, |
| | MECHANICAL, AND ZONING PLAN REVIEWERS. |
| | THE BUILDING REVIEW WILL BE FOR THE SLAB |
| | AND ANCHORING, (SUBMIT DETAIL - 140 |
| | MPH), ELECTRICAL REVIEW WILL BE FOR THE |
| | TRANSFER SWITCH AND DISTANCE FROM |
| | ELECTRICAL PANEL, (SUBMIT MANUF. |
| | SPECIFICATION SHEETS - MUST BE LISTED |
| | AND APPROVED), MECHANICAL REVIEW FOR THE |
| | EXHAUST, (PROPER CLEARANCES FROM |
| | OPENINGS IN HOUSES INCLUDING HOUSES ON |
| | ADJOINING PROPERTIES), AND ZONING, |
| | (SHOWING THE DISTANCE FROM PROPERTY |
| | LINES ECT.). SECTION 104.1.1. |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - SOME PIPE SIZES ARE NOT |
| | SHOWN. |
| | 3. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. - |
| | INDICATE PIPE MATERIAL TO GENERATOR. |
| | 4. SIGNATURE AND PRINTED NAME REQUIRED |
| | BY THE PERSON RESPONSIBLE FOR THE DESIGN |
| | ON EACH SHEET. SECTION 104.2.1. |
| | |