Plan Review Notes
Plan Review Notes For Permit 05051195
Permit Number 05051195
Review Stop G
Sequence Number 1
Notes
Date Text
2005-06-10 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1. NO PERMIT PERTAINING TO A GENERATOR
 SHALL BE ISSUED UNTIL AN APPLICATION FOR
 THE GENERATOR, (RES-GEN), WITH A REVIEW
 FOR THE GENERATOR BY BUILDING, ELECTRIC,
 MECHANICAL, AND ZONING PLAN REVIEWERS.
 THE BUILDING REVIEW WILL BE FOR THE SLAB
 AND ANCHORING, (SUBMIT DETAIL - 140
 MPH), ELECTRICAL REVIEW WILL BE FOR THE
 TRANSFER SWITCH AND DISTANCE FROM
 ELECTRICAL PANEL, (SUBMIT MANUF.
 SPECIFICATION SHEETS - MUST BE LISTED
 AND APPROVED), MECHANICAL REVIEW FOR THE
 EXHAUST, (PROPER CLEARANCES FROM
 OPENINGS IN HOUSES INCLUDING HOUSES ON
 ADJOINING PROPERTIES), AND ZONING,
 (SHOWING THE DISTANCE FROM PROPERTY
 LINES ECT.). SECTION 104.1.1.
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - SOME PIPE SIZES ARE NOT
 SHOWN.
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -
 INDICATE PIPE MATERIAL TO GENERATOR.
 4. SIGNATURE AND PRINTED NAME REQUIRED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN
 ON EACH SHEET. SECTION 104.2.1.
  