Plan Review Notes
Plan Review Notes For Permit 05051168
Permit Number 05051168
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-06 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL
 SCHEDULE(S).
 215.5
  
 2)NOTE: PLEASE SEE 210.12 2002 NEC FOR
 ARC FAULT PROTECTION FOR "ALL OUTLET" IN
 BEDRMS INCLUDING SD'S.
  
 3)NOTE: PLEASE INCLUDE CONDUCTOR SIZES
 AND OCP ON PANEL SCHEDULE.
 ALLL MUST MEET 2002 NEC,
 210.11C1,C3,424.3B,22
 PLEASE CORRELATE PANEL SCHEDULE WITH
 ITEMS SHOWN ON LOAD CALCULATIONS.
 215.5
  
 4)NOTE: PLEASE CLARIFY NEW OR EXISTING
 ELECTRICAL RISER SHOWN. IF NEW PLEASE
 COMPLETE RISER . SEC'S, CONDUITS, MAINS,
 OCP, AIC RATINGS, GROUNDING, ETC.
 110.9,250.50,310.16,240.3,,
  
 5)NOTE: PLEASE SEE RISER SHOWS ONE SUB
 PANEL? IS THIS HOUSE POWER? IS THIS THE
 PANEL TYPICAL FOR EACH UNIT?
 215.5
  
 6)NOTE: PLEASE SHOW PANEL LOCATIONS IN
 UNITS.
 215.5
  
 7)NOTE: PLEASE SHOW LOCATIONS OF ALL
 DISC'S FOR A/C EQUIPMENT.440.11
 PLEASE ALSO INLCUDE RECEPTS PER 210.63
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  