2005-06-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051113
 ADD: 515 N FLAGLER DR # 800
 CONT: BORAN, CRAIG,BBARBER, ENGELS
 TEL: (239)293-6822
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL S S 471.025/ FAC 61G15-23.002
 PLANS ARE TO BE DATED, WHEN SIGNING &
 SEALING FOR PUBLIC RECORD.
  
 2) SHEET A-2 INDICATES THE USE OF WOOD
 BUCKS, TYPE I & II BUILDINGS INTERIOR
 WALLS NON-COMBUSTIBLE SEE 604.
  
 3) THE EXISTING KITCHEN INSWING DOOR ;
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 BUILDING PLAN REVIEW