| Date |
Text |
| 2007-04-03 12:35:52 | ** UNSAT** |
| | |
| | *** PROVISO/REVISION NEEDED**** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE LOAD FOR THE AMOUNT OF RECESSED |
| | LIGHTING FIXTURES SHALL BE BASED ON THE FIXTURE WATTAGE |
| | BY THE NUMBER OF FIXTURES ON TOP OF THE 3WATTS PER SQ |
| | FT. |
| | THIS WAS TAKEN TO CODE PANELIST LAST YEAR TO CONFIRM |
| | THE SECTION OF 220.3B4. WHEN THE AMOUNT OF RECESSED |
| | LIGHTING IS FAR BEYOND WHAT WOULD BE NORMALLY |
| | CONSIDERED FOR THE GENERAL LIGHTING LOAD, THEN THE |
| | WATTAGE FOR FIXTURES ARE TO BE ADDED. |
| | THERE WAS NO CUT OFF FOR THE AMOUNT OF FIXTURES, AS IT |
| | WAS LEFT TO THE AHJ TO DETERMINE LOADS ON AN INDIVIDUAL |
| | BASIS WHEN REVIEWING THE AMOUNT OF FIXTURES. |
| | PLEASE SEE IN EITHER CASE THE LIGHTING IS NOT DE-RATED |
| | AT 50%. THERE IS NO LOCATION IN THE CODE WHERE LIGHTING |
| | LOADS PERMIT THIS DE-RATING FOR RESIDENTIAL USE. |
| | PLEASE SEE 220.30, 220.31. |
| | |
| | 2) NOTE: PLEASE SEE 250.66, 310.15B6 FOR THE MINIMUM |
| | GROUNDING ELECTRODE CONDUCTOR. |
| | |
| | 3) NOTE: PLEASE SEE 110.26 AS THE CU PANEL IS STILL |
| | BEING SHOWN BEHIND THE CONDENSING UNIT. |
| | PLEASE SEE THIS WAS REDLINED ON PLANS. |
| | |
| | ** PLANS WERE GIVEN A *PROVISO* UPON ISSUANCE TO HAVE |
| | ALL REVISIONS AND CORRECTIONS MADE BEFORE ROUGH AND |
| | THIS WAS NOT DONE. THE SERVICE AND SEVERAL OTHER |
| | CHANGES WERE MADE TO THE PLANS WITHOUT REVISIONS EVER |
| | BEING SUBMITTED. |
| | PLEASE KNOW THAT THE REVISED PLANS ARE TO BE 100%, |
| | SUBMITTED AND STAMPED FOR REVIEW BEFORE FINAL |
| | ELECTRICAL INSPECTION. |
| | PLANS WHICH ARE BEING STAMPED AT THIS TIME ARE ONLY FOR |
| | A PARTIAL FINAL OR TCO. |
| | PLEASE SUBMIT REVISED PLANS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |