| 2007-03-29 20:53:37 | |
| | |
| | ****** UNSAT ***** |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | |
| | ** PLEASE SEE THE PLANS SUBMITTED ARE NOW MORE COMPLETE |
| | PLANS FOR REVIEW FOR CODE COMPLIANCE. PLEASE SEE THERE |
| | ARE NEW COMMENTS BASED ON THE PLANS SUBMITTED. |
| | THE PREVIOUS REVIEW REQUESTED PLANS TO BE COMPLETED FOR |
| | CODE COMPLIANCE. |
| | |
| | 1) NOTE: PLEASE SEE ALL CIRCUITING HAS NOW BEEN REMOVED |
| | FROM PLANS. PLEASE SEE BY DOING SO SOME ITEMS DO NOT |
| | INDICATE HOW THEY ARE BEING CONTROLLED. |
| | PLEASE SEE OUTSIDE FLOODS? |
| | HOW ARE THESE CONTROLLED? |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE PANEL SCHEDULE IS NOT SHOWING ANY |
| | WIRE SIZES TO BE REVIEWED FOR CODE COMPLIANCE. 240.4, |
| | 310.16, 408.4 |
| | FBC 106.3.5.4. |
| | |
| | 3) NOTE: PLEASE CLARIFY THE SMOKE DEVICES AS SOME WHICH |
| | ARE BEING SHOWN AS SD ARE NOTED AS SMOKE DETECTORS AND |
| | SOME WITH THE S SYMBOLS ARE ALSO NOTED AS SMOKE |
| | DETECTORS? |
| | PLEASE SEE NFPA-72 DEFINITIONS FOR TYPES OF DEVICES. IF |
| | SMOKE ALARMS, INDICATE AS SA. |
| | PLEASE SEE THE PANEL SCHEDULE SHOWS THE 120VA HARDWIRED |
| | DEVICES AS SMOKE DETECTORS, WHICH IS NOT POSSIBLE. |
| | PLEASE SEE NOTE ON PANEL SCHEDULE WHICH ALSO MENTIONS |
| | SMOKE DETECTORS?? |
| | IF THERE ARE MULTIPLE TYPES OF DEVICES INSTALLED, |
| | PLEASE CLARIFY AND ALSO INDICATE IF TIED INTO A FA OR |
| | SECURITY SYSTEM W/ SOUNDING DEVICES. IF SD IS USED, |
| | THEN SOUNDING DEVICES ARE REQUIRED TO ALERT AN OCCUPANT |
| | IN THE EVENT OF ALARM STATUS. |
| | NFPA-72 2002 11.5.1.1.1, 11.8.3 |
| | |
| | 4) NOTE: PLEASE CORRELATE THE RISER WITH THE PANELS. |
| | PLEASE SEE PANEL *A* IS BEING SHOWN AS A 400A RATED |
| | PANEL WITH A 350AMP MAIN WHEN THE PANEL ON RISER IS |
| | SHOWN AS 200AMPS?? |
| | PLEASE KNOW THAT DEPENDING ON WHICH IS ACTUALLY |
| | INSTALLED; THE RISER MAY NEED TO BE COMPLETELY REVISED |
| | TO INCREASE SERVICE, CONDUCTORS GROUNDING ETC. 215.5, |
| | 310.16, 240.4 ETC. |
| | FBC 106.3.5.4 |
| | |
| | 5) NOTE: PLEASE SEE 310.15B6, 250.66 AS THE SERVICE IS |
| | BEING SHOWN AS 400AMPS, OR MORE DEPENDING ON NOTE #4 |
| | ABOVE. MINIMUM SIZE GEC IS 1/0. |
| | |
| | 6) NOTE: PLEASE SEE MISSING SMOKE ALARMS, OR SMOKE |
| | DETECTORS IN BEDROOMS ON 2ND FLOOR. BED-RM #4, AND |
| | OFFICE WHICH IS CONSIDERED AN ADAPTABLE SLEEPING ROOM. |
| | NFPA-72 11.5.1.1.1 |
| | |
| | 7) NOTE: PLEASE SEE THE VALUE FOR THE LOW VOLTAGE |
| | PERMIT AS PREVIOUSLY NOTED AHS NOT BEEN INCREASED BY |
| | THE CONTRACTOR. PLEASE KNOW THAT A VALUE WILL BE |
| | ASSESSED BY THIS OFFICE USING THE MARSHALL'S AND SWIFT |
| | GUIDE WHICH IS ADOPTED INTO THE FBC PER 108.3 |
| | |
| | 8) NOTE: PLEASE SEE 220.3B4 AS THE RECESSED LIGHTING AS |
| | REDLINED ON NOTES ON PREVIOUS PLANS NEEDS TO BE SHOWN |
| | IN LOAD CALCULATIONS. |
| | |
| | 9) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING |
| | KITCHEN COUNTERSPACES ARE TO BE SHOWN AS GFI OR GFI |
| | PROTECTED. |
| | |
| | ** PLEASE KNOW AS THE PLANS ARE NOT COMPLETE WITH SOME |
| | INFORMATION AS NEEDED FOR REVIEW, ONLY A REVIEW OF |
| | SUBMITTED PLANS COULD BE DONE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |