| 2007-03-08 15:45:33 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THE PLANS SUBMITTED ARE NOT |
| | COMPLETE AT THIS TIME FOR COMPLETE REVIEW OF CODE |
| | COMPLIANCE. |
| | PLEASE KNOW THAT THERE MAY BE COMMENTS ONCE PLANS ARE |
| | COMPLETE. |
| | |
| | 2) NOTE: PLEASE SEE *PROVISO* WHICH WAS GIVEN IN |
| | SEPTEMBER OF 05 WHICH REQUIRED THOSE ITEMS TO BE |
| | REVISED *BEFORE ROUGH*. THIS WAS NOT DONE YET ROUGH |
| | ELECTRICAL INSPECTION WAS CALLED IN WITH NOTES ATTACHED |
| | TO PLANS. |
| | INSPECTOR INFORMED THIS OFFICE THAT THE NOTES WHICH |
| | WERE ATTACHED TO PLANS WERE TORN OFF. |
| | PLEASE COMPLETE THE FOLLOWING. |
| | |
| | PLEASE COMPLETE ALL CIRCUITING ON PLANS AND CORRELATE |
| | WITH REVISED PANEL SCHEDULES TO BE REVISED AND |
| | SUBMITTED. PLEASE SEE MANY ITEMS ON PLANS DO NOT |
| | CONTAIN CIRCUITING AND REVIEW FOR CODE COMPLIANCE CAN |
| | NOT BE DONE AT THIS TIME. |
| | PLEASE COMPLETE AND SUBMIT LOAD CALCULATIONS PER NEC. |
| | PLEASE CORRELATE LOADS ON PANEL SCHEDULES AND COMPLETE |
| | AS REQUIRED PER CODE AND PREVIOUS *PROVISO *NOTES. |
| | PLEASE SUBMIT THE COMPLETE ELECTRICAL RISER DIAGRAM TO |
| | BE REVIEWED FOR CODE COMPLIANCE. |
| | PLEASE BE SURE TO SEE THE 2002 NEC. |
| | 210.52,210.11, 220, 310.16, 240.4 ETC |
| | FBC 106.1.2, 106.3.5.4 ETC. |
| | |
| | 3) NOTE: PLEASE SEE THE DEVICES WHICH ARE SHOWN AS |
| | SMOKE DETECTORS SHOULD BE SHOWN AS SMOKE ALARMS IF THEY |
| | ARE 120V WITH DETECTION AND SOUNDING IN THE SINGLE |
| | UNIT. |
| | PLEASE SEE NFPA-72 DEFINITIONS FOR THE DIFFERENCES FROM |
| | SMOKE DETECTORS AND SMOKE ALARMS. |
| | |
| | 4) NOTE: PLEASE SEE THERE ARE NOW NUMEROUS LOW VOLTAGE |
| | ITEMS ON PLANS WHICH THE LOW VOLTAGE PERMIT WAS UNDER |
| | VALUED BASED ON PLANS. |
| | PLEASE HAVE THE CONTRACTOR INCREASE VALUE FOR ALL LV |
| | WORK AS SHOWN WHICH SHALL INCLUDE ALL LABOR AND |
| | MATERIALS EVEN IF OWNER SUPPLIED. |
| | PLEASE KNOW A VALUE MAY BE ACCESSED BY THIS OFFICE IF |
| | AN APPROPRIATE VALUE IS NOT APPLIED.** |
| | FBC 108.3 |
| | |
| | ** PLEASE KNOW A HOLD IS NOW BEING PLACED ON THE |
| | ELECTRICAL AND BUILDING PERMIT ON INSPECTIONS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |