| 2006-02-15 00:00:00 | ********** UNSAT ************* |
| | |
| | |
| | 1)NOTE: PLEASE SEE "PROVISO" NOTES FROM |
| | 9/29/05 WHICH HAVE NOT BEEN ADDRESSED OR |
| | SUBMITTED. |
| | PLEASE SEE THE PERMIT WAS ISSUED ON THE |
| | CONDITION THESE ITMES BE ADDRESSED, CODE |
| | COMPLIANT AND RETURNED FOR REVIEW. |
| | PLEASE SEE NOTES BELOEW. |
| | |
| | 2)NOTE: PLEASE CORRELATE ALL PANELS, |
| | LOADS ETC. |
| | PLEASE SUBMIT LOADS CALCUALTIONS WHICH |
| | MEET THE NEC 220 |
| | PLEASE CORRELATE LOADS ON PANELS ETC. |
| | PLEASE RE-FIGURE AS REQUESTED ON |
| | PREVIOUS REVIEW. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE MANY ITEMS FOR |
| | PREVIOUS "PROVISO" CAN BE REVIEWED FOR |
| | CORRECTED ITEMS AS THE FIRST FLR PLANS |
| | WERE NOT SUBMITTED.? |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE RISER HAS NOW BEEN |
| | REVISED TO REMOVED GROUNDING ELECTODE |
| | ATTACHMENT TO FOOTER STEEL, HOWEVER THIS |
| | ATTACHMENT FOR NEW CONSTRUCTION IS |
| | REQUIRED TO BE INSTALLED PER 250.50, |
| | 250.52A |
| | THIS SHALL NOT BE DELETED FROM PLANS AND |
| | RISER. |
| | |
| | 5)NOTE: PLEASE SEE A NEW DETAIL WAS |
| | SUBMITTED FOR A "HURRICANE ROOM" HOWEVER |
| | PLANS WERE NOT REVISED TO SHOW THIS |
| | ROOM, LTS, RECEPTS ETC. 210.52,210.70 |
| | ETC. |
| | PLEASE ALSO SEE BLDG COMMENTS AS THE |
| | 8 1/2X 11 IS MISSING THE TITLE BLOCK FOR |
| | ARCHITECT AND OTHER POSSIBLE INFORMATION |
| | NEEDED FOR BLDG REVIEW. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | AND OTHER INFORMATION FOR REVIEW. |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |