| 2005-09-29 00:00:00 | ********** PROVISO/ REVISION ********** |
| | |
| | PLEASE SEE ITEMS BELOW ALONG WITH ANY |
| | OTHER REVISIONS MUST BE SUBMITTED FOR |
| | REVIEW AND STAMPING BEFORE ANY ROUGH |
| | ELECTRICAL INSPECTION. |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE SMOKE DETECTORS ARE |
| | REQUIRED ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING LEADING TO THE FLOOR ABOVE IN |
| | THE IMEDIATE VICINITY OF STAIRS. |
| | PLEASE SEE MISSING SD AT REAR FOYER |
| | LOWER LEVEL. |
| | PLEASE SEE SD AT FRONT FOYER REQUIRED ON |
| | WALL NO MORE THAN 10' ABOVE FF. |
| | |
| | 2)NOTE: PLEASE SEE MIN CONTROL AND |
| | EGRESS LIGHT FIXTURE(S) REQUIRED AT REAR |
| | FOYER ENTRY/ EXIT. |
| | PLEASE ALSO SEE MEANS OF EGRESS FROM |
| | LAUNDRY RM AND BEDRM #3.3-WAY/4-WAY |
| | SWITCHES REQUIRED. |
| | PLEASE SEE SEE A "GAS FIXURE" MAY BE |
| | INSTALLED ALSO, HOWEVER AN ELECTRICAL SW |
| | AND FIXTURE IS REQUIRED. |
| | PLEASE SEE FRONT PORCH IS OK, DUE TO |
| | ELECTRICAL RECESSED LTS ALONG W/GAS FIX. |
| | 210.70, LS 101 7.8 |
| | |
| | 3)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 |
| | |
| | 4)NOTE: PLEASE SEE "DEN" RECEPTS (A-32) |
| | CIRCUITED TO SMALL APPL CIRCUIT. |
| | BRKFST AREA, DINING AREA MAY NOT FEED |
| | OTHER ARES. |
| | PLEASE ADJUST. |
| | |
| | 5)NOTE: PLEASE CORRELATE ALL LOADS ON |
| | PANELS AND LOAD CALCUALTIONS. |
| | PLEASE GO THROUGH LOAD CALCULATIONS AND |
| | RE-FIGURE TO MEET NEC 220. |
| | PANEL "A" SHOWS 30KVA FOR PANEL "B", |
| | HOWEVER PANEL "B" SHOWS 40KVA. |
| | SEE PANEL "C" ETC. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |