| 2005-09-07 00:00:00 | *** DENIED *** | | | 1) PLEASE SHOW WHICH SUB-SECTION OF | | | SECTION 703 FBC/M 2001 YOU ARE USING | | | TO OBTAIN COMBUSTION AIR FOR THE | | | LAUNDRY ROOM. | | | 2) SUPPLY AIR DUCTS (MAIN TRUNK LINES & | | | BRANCH LINES) ARE NOT PROPERLY SIZED | | | FOR ADEQUATE AIR DISRIBUTION. | | | 3) RETURN AIR DUCTS TO AHU'S ARE NOT | | | PROPERLY SIZED PER 2001 FBC/M 601.4. | | | 4) RETURN AIR GRILLS TO AHU'S ARE NOT | | | SIZED (18"X18" WOULD BE TO SMALL). | | | 5) SUPPLY AIR DUCTS CAN NOT GO TO | | | CLOSETS IN GARAGE (HAZARDOUS FUMES | | | MAY ENTER DUCTS WHEN UNIT IS NOT | | | RUNNING). | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|