| 2005-08-31 00:00:00 | *********UNSAT 2ND REVIEW ****** |
| | |
| | PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| | REVIEW AND SOME NEW COMMENTS DUE TO |
| | CHANGES IN PLANS. |
| | |
| | 1)NOTE; 210.8A6,INDICATE GFI'S ALONG |
| | KITCHEN COUNTERSPACES, REDLINED ONE. |
| | SEE PLANS. |
| | |
| | 2)NOTE: PLEASE SEE NFPA-72, 8-1.4.2, |
| | WHICH REQUIRES SD'S TO BE MIN OF 3' FROM |
| | BATH DRS. |
| | PLEASE SEE REDLINED PLANS FOR THESE. |
| | PLEASE SEE "GREAT RMM" APPEARS TO SHOW |
| | TWO SD'S ?? |
| | THIS IS OK, BUT NOT REQUIRED.(FYI). |
| | |
| | 3)NOTE: PLEASE SHOW ALL SERVICE |
| | EQUIPMENT ON PLANS CORRELATE WITH RISER |
| | DIAGRAM SUBMITTED. |
| | PLEASE SEE PLANS DO NOT SHOW LOCATION OF |
| | METER/SERVICE. |
| | PLEASE SEE TRANSFER SWITCH IS STILL |
| | SHOWN ON PLANS, HOWEVER THIS HAS NOW |
| | BEEN REMOVED FROM RISER? |
| | |
| | 4)NOTE:PLEASE SEE CIRCUITING FOR MIN |
| | DINING RM, ETC RECEPTS WERE REVISED, |
| | HOWEVER, PLEASE SEE CIRCUIT A-32 WHICH |
| | SHARES BRKFAST AREA AND DEN AREA. |
| | PLEASE SEE 210.52B1, OTHER OUTLETS MAY |
| | NOT BE ON THESE CIRCUITS. |
| | PLEASE SEE REDLINED RECEPTS ON PLANS IN |
| | DEN. |
| | |
| | 5)NOTE: : PLEASE SEE REDLINED PLANS FOR |
| | SOME RECEPTS MISSING FOR 2' OF WALL |
| | SPACE AND WITH 6' OF DOORWAY. . |
| | 210.52.2ND FLR. |
| | |
| | 6)NOTE:PLEASE CORRELATE LOAD |
| | CALCUALTIONS NOW SUBMITTED. PLEASE SEE |
| | THE LOADS SEEM TO HAVE BEEN ROUNDED DOWN |
| | FOR EACH AND SERVICE. PLEASE SEE LOADS |
| | MAY BE ROUNDED UP , BUT CAN BE ROUNDED |
| | DOWN. |
| | PLEASE SEE REDLINED PLANS. |
| | PLEASE SEE POOL PANEL INDICATES 3.4KW |
| | AND PANEL "B" SHOWS 4.2? |
| | PLEASE SEE PANEL "A" SHOWS KW RATING FOR |
| | PANEL "B" AS 15KW, HOWEVER PANEL "B" |
| | INDICATES LOAD AT 39.9 WHICH DOES NOT |
| | SEEM TO CORRELATE WITH LOAD CALCS OR |
| | PANEL "A"? |
| | PLEASE SEE 220.31. |
| | |
| | 7)NOTE: PLEASE SEE FS 553.80(2)(B), THIS |
| | IS ONLY A NOTICE. |
| | |
| | PLEASE BE SURE TO SEE ANY COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. (ZONING ETC) |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM |
| | SETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SEE ALL OTHER COMMENTS FOR |
| | GENERATOR WILL NOT BE INCLUDED. |
| | PLEASE BE SURE TO SEE COMMENTS DUE TO |
| | PLANNING FOR LOCATION OF FUTURE |
| | EQUIPMNET. MAINS AND DISCONNECTING MEANS |
| | SHALL BE GROUPED. |
| | 230.72, 225.34, 225.31 |
| | PLEASE CALL IF THERE ARE ANY QUESTIONS, |
| | ON THIS. |
| | |
| | PLEASE SUBMIT THE ABVOE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CAONTACTING |
| | THIS OFFICE. |
| | |