| Date |
Text |
| 2005-06-15 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1. SHT P2.2 THE SANITARY RISER DIAGRAM |
| | DOES NOT MEET CODE REQUIREMENTS. CORRECT |
| | THE FOLLOWING. |
| | A. VENT REQUIRED AT LAV FIRST FLOOR |
| | POWDER ROOM . SECTION 901.2.1 |
| | B. CLEANOUT IS REQUIRED AT THE BASE OF |
| | THE STACK TO THE SECOND FLOOR. SECTION |
| | 708.3.4. |
| | C. SIZE ALL PIPE SECTIONS PER TABLE |
| | 710.1(1). |
| | D. VENTS ARE REQUIRED FOR BOTH KITCHEN |
| | SINKS. SECTION 901.2.1. |
| | E. VENTS REQUIRED FOR LAV NEAR THE |
| | GARAGE AND THE SINK IN THE GARAGE. |
| | SECTION 901.2.1. |
| | F. GARAGE SINK SHALL NOT DRAIN THROUGH |
| | THE HORIZONTAL WET VENT OF THE POWDER |
| | ROOM FIXTURES. SECTION 909.1. SINK SHALL |
| | DISCHARGE DOWNSTREAM OF FIXTURES. |
| | G. VENT REQUIRED FOR THE SECOND FLOOR |
| | DOUBLE LAVS. SECTION 104.2.1. |
| | H. W/C AND TUB ARE NOT VENTED AS PIPED |
| | FOR BATHROOM WITH THE DOUBLE LAVS, AND |
| | THE WASH MACHINE SHALL NOT DRAIN THROUGH |
| | THE HORIZONTAL WET VENT OF THAT |
| | BATHROOM. SECTIONS 901.2.1. & 909.1. |
| | I. VENTS ARE REQUIRED FOR THE TUB AND |
| | SINK NEAR AND AT THE GREAT ROOM. SECTION |
| | 901.2.1. |
| | J. THE GREAT ROOM SINK SHALL NOT DRAIN |
| | THRU THE HORIZONTAL WET VENT OF THE |
| | BATHROOM FIXTURES. THIS SINK SHALL |
| | DISCHARGE DOWNSTREAM OF THE BATHROOM |
| | FIXTURES. SECTION 909.1 |
| | K. A VENT, A STANDPIPE AND A CLEANOUT |
| | ARE REQUIRED FOR THE WASH MACHINE. THE |
| | CLEANOUT SHALL BE LOCATED 4' ABOVE THE |
| | FLOOR. SECTIONS 708.10, 901.2.1 AND |
| | 1002.1. |
| | L. VENTS ARE REQUIRED FOR BOTH LAVS IN |
| | THE MASTER BATHROOM. SECTION 901.2.1. |
| | M. FITTINGS CONNECTING THE ISLAND SINK |
| | IN THE KITCHEN AND THE TUB IN THE MASTER |
| | BATHROOM DO NOT GUIDE THE WASTE IN THE |
| | DIRECTION OF FLOW AS REQUIRED IN SECTION |
| | 706.3. |
| | 2. SEE RED LINE CORRECTIONS ON ONE SET |
| | OF PLANS AS AN EXAMPLE TO AID IN |
| | CORRECTING THE CODE VIOLATIONS. |
| | 3. GAS INDICATED ON PLANS. SEPARATE |
| | PLANS AND PERMIT REQUIRED FOR GAS. SEE |
| | ATTACHED SHEET FOR GAS PERMIT |
| | APPLICATION REQUIREMENTS. |
| | |