| 2005-06-15 00:00:00 | DENIED: |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW; |
| | 1.PLAN SHEET P2.1 INDICATES A GAS FIRE |
| | PLACE.PLEASE PROVIDE MANUFACTURER'S |
| | SUBMITTAL DATA.PROVIDE COMBUSTION AIR |
| | CALUCALTIONS AND MAKE-UP AIR (IF |
| | REQUIRED). |
| | |
| | 2.PLAN SHEET P2.2 INDICATES A GAS |
| | DRYER.PLEASE PROVIDE CALCUALTIONS FOR |
| | COMBUSTION AIR AND AIR MAKE UP PER |
| | CHAPER 7 OF THE 2001 FBC(M). |
| | |
| | 3.PLANS DO NOT INDICATE ACCESS OR |
| | HANGING DETAIL FOR THE AHU'S 1 & 2. |
| | SHOW COMPLAINCE WITH 2001 FBC CHAPTER 13 |
| | SUB-CHAPTER 610.1.ABC.3.5. |
| | |
| | 4.AUXILIARY DRAIN PAN WITH OVERFLOW |
| | PROTECTION REQUIRED PER 2001 |
| | FBC(M)307.2.3.NOTE ON PLAN SHEET M2.1 |
| | INDICATES THE REQUIREMENT FOR THE PAN |
| | BUT ONLY MENTIONS CONDENSATE LINE. |
| | SECONDARY DRAIN LINE SHALL TERMINATE AT |
| | A CONSPICUOUS POINT. |
| | |
| | 5.CONDENSATE SHALL TERMINATE A MINIMUM |
| | OF 12" AWAY FROM THE BUILDING STRUCTURE |
| | PER 2001 FBC 1503.4.4. |
| | |
| | 6.INDICATE LINE SIZE FOR THE |
| | CONDESATE, AND REFRIGERANT LINES. |
| | |
| | 7.CONDENSING UNITS BE SUPPORTED BY A |
| | LEVEL CONCRETE SLAB A MINIMUM OF 3 1/2 |
| | THICKEXTENDING A MINIMUM OF 2" ABOVE |
| | THE ADJOINING GRADE. |
| | |
| | 8.PLANS DO NOT INDICATE TIE DOWN OR |
| | ANCHORING FOR THE CONDENSING UNIT. |
| | PLEASE REFERENCE 2001 FBC(M)301.13.1. |
| | |
| | 9.PROVIDE GRILLE SIZES.ALSO MISSING |
| | RETURN AIR DUCT & JUMPER SIZES.PLEASE |
| | NOTE,SQUARE INCHES OF THE RETURN AIR |
| | JUMPERS ARE TO BE A MINIMUM OF 1 1/2 |
| | TIMES GREATER THAN THE SUPPLY AIR INTO |
| | THAT SPACE. |
| | |