| Date |
Text |
| 2005-06-07 00:00:00 | ********** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE PERMIT APPLICATION |
| | MENTIONS "APPROACH AND DRIVEWAY FOR NEW |
| | TWO STORY HOUSE" PLEASE ADJUST PERMIT |
| | APPLICATION FOR NEW TWO STORY HOUSE. |
| | |
| | 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | PLEASE SEE AREA(S) TO BE INCLUDED AS |
| | KITCHEN COUNTERSPACE AREA. |
| | |
| | 3)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2 |
| | 8-1.4.2 |
| | |
| | 4)NOTE: PLEASE SEE MIN CLEARENCE |
| | REQUIRED FOR A/C DISC'S. 110.26 |
| | |
| | 5)NOTE: PLEASE SHOW ALL SERVICE |
| | EQUIPMENT ON PLANS. IF GENERATOR IS TO |
| | BE INCLUDED UNDER ELECTRICAL PERMIT FOR |
| | MAIN HOUSE. SITE PLAN, SURVEY ETC MUST |
| | SHOW LOCATION OF GEN. ALSO. |
| | PLEASE ALSO SEE OTHER COMMENTS FOR GEN |
| | TO FOLLOW. |
| | |
| | 6)NOTE: PLEASE PROVIDE ROMM DESIGNATION |
| | ON PLANS. |
| | 215.5 |
| | |
| | 7)NOTE: PLEASE SEE CIRCUITING OF DINING |
| | RM, BREAKFAST AREAS AND THE LIKE PER |
| | 210.52-B-1. |
| | |
| | 8)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | PLEASE SEE 210.12 2002NEC. |
| | |
| | 9)NOTE: PLEASE SEE ROOM ABOVE GARAGE. |
| | PLEASE SEE RECEPTS WHICH APPEAR TO BE |
| | FLOOR RECEPTS?? OR ARE THESE |
| | MIS-LOCATED.? 210.52 |
| | PLEASE ALSO SEE OTHER MISSING RECEPTS |
| | MISSING FOR 2' OF WALL SPACE. |
| | |
| | 10)NOTE: PLEASE SEE CIRCUITING FOR BATH |
| | GFI RECEPTS IN MASTER BATH. |
| | PLEASE SEE 210.11C3, 210.52D |
| | PLEASE SEE THERE SHALL BE NO OTHER |
| | RECEPTS/OUTLETS EXCEPT FOR THOSE IN |
| | BATHRM. |
| | |
| | 11)NOTE: PLEASE SEE PLANS INDICATE "SPA" |
| | RECEPT FOR MASTER BATH. |
| | PLEASE SEE PANEL SCHEDULE DOES NOT |
| | INDICATE THIS. PLEASE ALSO ADJUST LOAD |
| | CALCULATIONS TO INCLUDE LOAD AND PLEASE |
| | SHOW AS GFI /GFI PROTECTED . |
| | 215.5,220.31,680.71 |
| | |
| | 12)NOTE: PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS FOR EACH PANEL. |
| | PLEASE CORRELATE LOADS ON PANEL |
| | SCHEDULES AND SERVICE RISER LOAD CALCS. |
| | PLEASE CORRELATE LOAD(S) FOR SUB |
| | PANEL(S). PLEASE SEE PANEL "A" SHOWS THE |
| | SAME LOAD AS SUB PANEL "B" , YET LOADS |
| | IMPOSED ON EACH PANEL(BY PANEL SCHEDULE) |
| | ARE COMPLETELY DIFFERENT. |
| | 220,215.5 ETC. |
| | PLEASE ALSO INCLUDE SIZE OF METERCAN TO |
| | BE PROVIDED. |
| | |
| | 13)NOTE: PLEASE SEE SUB PANEL FOR POOL |
| | IS MISSING FROM RISER, PANEL SCHEDULES |
| | ETC.215.5 |
| | |
| | 14)NOTE: PLEASE CORRELATE DESCRIPTION |
| | FOR PANEL "B". PLEASE SEE PANEL SHOWN AS |
| | 42 CIR, HOWEVER PANEL MENTIONS 30?? |
| | 215.5 |
| | |
| | 15)NOTE: PLEASE SEE 250.50 WHICH |
| | REQUIRES THE "FOOTER STEEL" TO BE PART |
| | OF THE GROUNDING ELECTRODE SYSTEM. |
| | PLEASE SEE RISER MENTIONS STRUCTUAL |
| | STEEL. IF THE CONSTRUCTION OF THE HOUSE |
| | ALSO INCLUDES "STRUCTUAL STEEL" THEN IT |
| | WOULD ALSO BE INCLUDED AS PART IF THE |
| | GES. 250.50 |
| | |
| | PLEASE SEE THE FOLLOWING COMMENTS FOR |
| | GEN/ATS ETC. |
| | "IF" GENERATOR IS TO BE INCLUDED AS PART |
| | OF THESE PLANS AND UNDER THE ELECTRICAL |
| | PERMIT FOR THE HOUSE, THEN ALL OF THE |
| | FOLLOWING INFORMATION MUST BE INCLUDED |
| | WITH THIS PERMIT APPLICATION PACKAGE. |
| | |
| | |
| | 16)NOTE: PLEASE SUBMIT COMLPETE SITE |
| | PLAN SHOWING GEN LOCATIONS ALONG WITH |
| | ANY OTHER EQUIPMENT WHICH MAY NEED TO BE |
| | INCLUDED. THIS MUST ALSO BE INCLUDED ON |
| | SURVEY SHOWING ALL DIMENIONS. |
| | FUEL STORAGE TANK? ETC. |
| | PLEASE ALSO SUBMIT ELEVATIONS FOR |
| | EQUIPMENT WHICH MUST MUST BE ABOVE BASE |
| | FLOOD ELEVATION. |
| | 700.9 AND FEMA REGULATIONS OF UTILITY |
| | EQUIPMENT. |
| | |
| | 17)NOTE: PLEASE INDICATE THE PRIME MOVER |
| | FOR GEN. |
| | 215.5,700.12B1-2 ETC |
| | |
| | 18)NOTE: PLEASE SEE STRUCTURAL DETAIL9S0 |
| | MUST BE SUBMITTED FOR BLDG REVIEW FOR |
| | ATTACHMENT OF GEN TO SLAB/ FBC 140MPH |
| | WIND LOAD. |
| | |
| | 19)NOTE: PLEASE NOTE/KEEP IN MIND MIN |
| | CLEARENCE FROM WINDOW/DOOR AND ATTIC |
| | OPENINGS. A MIN OF 10" IS REQUIRED FOR |
| | EXHAUST. SEE MECH CODE FOR MIN |
| | REQUIREMENTS. THIS IS NOT AN ELECTRICAL |
| | CODE. |
| | |
| | 20)NOTE: PLEASE SUBMIT COMPLETE |
| | MANUFACTTURE CUT/SPEC SHEETS FOR |
| | GENERATOR, AND ATS. |
| | PLEASE BE SURE ALL MEET 702.3-702.6. |
| | 225.31-225.36 |
| | |
| | 21)NOTE: PLEASE SEE MEANS OF DISC MUST |
| | MEET 225.31-225.36. |
| | NO DISC IS SHOWN ON LINE SIDE OF ATS. |
| | NO INFORMATION FOR ATS IS PROVIDED. |
| | SIZE? |
| | PLEASE SEE THE MEANS OF DISC IS REQUIRED |
| | TO BE LOCATED ADJACENT TO OR BACK TO |
| | BACK WITH TRANSFER SWITCH. |
| | 215.5 |
| | |
| | 22)NOTE: PLEASE CORRELATE PLANS WITH |
| | RISER DIAGRAM. PLEASE SEE PLANS MENTIOSN |
| | AN ATS (AUTOMATIC TRANSFER SWITCH) YET |
| | RISER MENTIONS A MANUAL TRANSFER |
| | SWITCH(MTS). |
| | PLEASE SEE 702.5, IF SYSTEM IS GOING TO |
| | BE AN "AUTOMATIC" SYSTEM, THEN GEN. IS |
| | REQUIRED TO BE SIZED FOR SERVICE/LOAD |
| | CALCULATIONS AS SHOWN. |
| | MEANS OF LOAD SHEEDING (IF) PROVIDED |
| | WOULD NEED TO BE SHOWN IN DETAIL. |
| | 215.5 |
| | |
| | 23)NOTE: PLEASE INCLUDE CONDUCTORS FROM |
| | TRANSFER SWITCH TO MCB PANEL. |
| | PLEASE SEE 250.24, 250.6 IF FIRST MEANS |
| | OF DISC IS PROVIDED. |
| | |
| | 24)NOTE: PLEASE BE SURE TO NOTE WHEATHER |
| | OR NOT GEN IS TO BE SEPARATELY DERIVED |
| | OR NOT.. |
| | |
| | PLEASE SEE MANY OF THE ABOVE LOCATIONS |
| | HAVE BEEN REDLIND ON ONE SET OF PLANS |
| | FOR COMMENTS ABOVE. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT "ONE" SET OF OLD/VOIDED |
| | SHEETS FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |