| 2005-08-12 00:00:00 | DENIED |
| | |
| | 1. 713.13(2) F.S.THE NOTICE OF |
| | COMMENCEMENT MUST BE RE-RECORDED BECAUSE |
| | THE DESCRIBED IMPROVEMENT OR |
| | CONSTRUCTION DID NOT COMMENCE WITHIN 90 |
| | DAYS OF RECORDING. |
| | |
| | 3.BUILDING IS IN FLOOD ZONE "A". |
| | SHOW THAT THE MINIMUM BASE FLOOD |
| | ELEVATION IS 7 FT. AND THE MINIMUM |
| | FINISH FLOOR HEIGHT IS 6" ABOVE THAT. |
| | |
| | 4.SUBMIT TWO COPIES OF PRODUCT |
| | APPROVALS FOR SLOPED ROOF, STRAPS AND |
| | TIEDOWNS AND SKYLIGHT |
| | ** ALL MIAMI-DADE PRODUCT APPROVALS |
| | REQUIRE THE FOLLOWING TO BE ATTACHED** |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |
| | |