2006-12-05 14:04:48REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SANITARY RISER DIAGRAM DOES NOT MEET CODE
 REQUIREMENTS, NOR DOES IT REFLECT THE FLOOR PLAN.
 PLEASE CORRECT THE FOLLOWING:
 A. KITCHEN SINK FITTINGS DO NOT DIRECT WASTE IN THE
 DIRECTION OF FLOW. SECTION 706.3.
 B. THE SINK IN THE LAUNDRY ROOM IS NOT SHOWN ON THE
 RISER DIAGRAM. SECTION 104.2.1, AND TABLE 710.1(2).
  
 C. THE WASH MACHINE REQUIRES A STANDPIPE. SECTIONS
 802.4 & 1002.1.
 D. THE CLEANOUT FOR THE WASH MACHINE SHALL BE LOCATED
 4' ABOVE THE FLOOR FOR ACCESS. SECTION 708.10.
 E. SHOW ALL PIPE SIZES. TABLE 710.1(2).
 F. BRANCH PIPING FROM 2ND FLOOR BATHROOM CONNECTED TO
 3 STACKS. TWO VENT STACKS AND ONE SANT. STACK. PLEASE
 CHANGE ROUTING. SECTIONS 706.3 & 908.3.
 (SEE RED LINE EXAMPLESON ONE REVISED DIAGRAM).
  