| Plan Review Notes For Permit 05051065 |
| Permit Number |
05051065 |
|
| Review Stop |
P |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2006-12-05 14:04:48 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1. SANITARY RISER DIAGRAM DOES NOT MEET CODE | | | REQUIREMENTS, NOR DOES IT REFLECT THE FLOOR PLAN. | | | PLEASE CORRECT THE FOLLOWING: | | | A. KITCHEN SINK FITTINGS DO NOT DIRECT WASTE IN THE | | | DIRECTION OF FLOW. SECTION 706.3. | | | B. THE SINK IN THE LAUNDRY ROOM IS NOT SHOWN ON THE | | | RISER DIAGRAM. SECTION 104.2.1, AND TABLE 710.1(2). | | | | | | C. THE WASH MACHINE REQUIRES A STANDPIPE. SECTIONS | | | 802.4 & 1002.1. | | | D. THE CLEANOUT FOR THE WASH MACHINE SHALL BE LOCATED | | | 4' ABOVE THE FLOOR FOR ACCESS. SECTION 708.10. | | | E. SHOW ALL PIPE SIZES. TABLE 710.1(2). | | | F. BRANCH PIPING FROM 2ND FLOOR BATHROOM CONNECTED TO | | | 3 STACKS. TWO VENT STACKS AND ONE SANT. STACK. PLEASE | | | CHANGE ROUTING. SECTIONS 706.3 & 908.3. | | | (SEE RED LINE EXAMPLESON ONE REVISED DIAGRAM). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|