| Date |
Text |
| 2006-03-14 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} SUBMIT THE AIC RATING OF THE SERVICE |
| | EQUIPMENT PER 110.9 AND 110.10. |
| | |
| | 2} PROVIDE AN EQUIPMENT GROUND FROM THE |
| | DISCONNECTING MEANS TO THE PANELS PER |
| | 250.122. SEE RISER. |
| | |
| | 3} THE RISER HAS BOTH PANELS LABLED "A". |
| | THERE IS ALSO SOME CONFUSION ON THE |
| | PANEL SCHEDULES. PLEASE CORRELATE. |
| | |
| | 4} THE KITCHEN COUNTERTOP RECEPTACLES |
| | MUST BE GFI PROTECTED PER 210.8(A)(6), |
| | PLEASE INDICATE SAME ON PLANS. |
| | |
| | 5} THE MASTER BATH MUST IS REQUIRED TO |
| | HAVE RECEPTACLE SPACING PER 210.52(D). |
| | ONE MUST BE ADDED OR THE ONE SHOWN MUST |
| | BE RELOCATED. |
| | |
| | 6) THE SPA IN THE MASTER BATH MUST BE |
| | PROTECTED BY A GFI PER 680.44. |
| | |
| | 7} THE NURSERY AND THE GUEST BEDROOM |
| | MUST HAVE RECEPTACLES ADDED PER |
| | 210.52(A)(1). SEE REVIEWED SET. |
| | |
| | 8} A SMOKE DETECTOR IS REQUIRED OUTSIDE |
| | THE BEDROOM UPSTAIRS PER R 313.1 FBC. |
| | |
| | 9} THE ARCHITECT MUST DATE THE SEAL PER |
| | 61G1-16.004 FAC, ALL SHEETS. |
| | |
| | IF THERE ARE ANY QUESTIIONS PLEASE CALL. |
| | |