Plan Review Notes
Plan Review Notes For Permit 05051065
Permit Number 05051065
Review Stop E
Sequence Number 3
Notes
Date Text
2006-03-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT THE AIC RATING OF THE SERVICE
 EQUIPMENT PER 110.9 AND 110.10.
  
 2} PROVIDE AN EQUIPMENT GROUND FROM THE
 DISCONNECTING MEANS TO THE PANELS PER
 250.122. SEE RISER.
  
 3} THE RISER HAS BOTH PANELS LABLED "A".
 THERE IS ALSO SOME CONFUSION ON THE
 PANEL SCHEDULES. PLEASE CORRELATE.
  
 4} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST BE GFI PROTECTED PER 210.8(A)(6),
 PLEASE INDICATE SAME ON PLANS.
  
 5} THE MASTER BATH MUST IS REQUIRED TO
 HAVE RECEPTACLE SPACING PER 210.52(D).
 ONE MUST BE ADDED OR THE ONE SHOWN MUST
 BE RELOCATED.
  
 6) THE SPA IN THE MASTER BATH MUST BE
 PROTECTED BY A GFI PER 680.44.
  
 7} THE NURSERY AND THE GUEST BEDROOM
 MUST HAVE RECEPTACLES ADDED PER
 210.52(A)(1). SEE REVIEWED SET.
  
 8} A SMOKE DETECTOR IS REQUIRED OUTSIDE
 THE BEDROOM UPSTAIRS PER R 313.1 FBC.
  
 9} THE ARCHITECT MUST DATE THE SEAL PER
 61G1-16.004 FAC, ALL SHEETS.
  
 IF THERE ARE ANY QUESTIIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  