| Plan Review Notes For Permit 05051065 |
| Permit Number |
05051065 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-01-23 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} TWO SMALL APPLIANCE CIRCUITS ARE | | | REQUIRED IN THE KITCHEN PER 220.16. | | | PLEASE ADD IN CALCULATIONS. | | | | | | 2} PLEASE PROVIDE A AIC RATING PER 110.9 | | | & 10. | | | | | | 3} A COUNERTOP RECEPTACLE PER | | | 210.52(C)(3) MUST BE INSTALLED ON THE | | | PENINSULA. | | | | | | 4} PLEASE SEE ARTICLE 11.8.3.5(4) | | | REGARDING LOCATION AND TYPE OF SMOKE | | | DETECTORS ACCEPTABLE IN THE KITCHEN. | | | | | | 5} THE MASTER BEDROOM, NURSERY AND BOTH | | | ROOMS ON THE SECOND LEVEL REQUIRE | | | RECEPTACLES TO COMPLY WITH 210.52(A)(1) | | | &(2). | | | | | | 6} ELECTRIC PANEL "B" SEEMS TO BE DRAWN | | | FREESTANDING. PLEASE SHOW IN CORRECT | | | LOCATION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|