Plan Review Notes
Plan Review Notes For Permit 05051065
Permit Number 05051065
Review Stop E
Sequence Number 2
Notes
Date Text
2006-01-23 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} TWO SMALL APPLIANCE CIRCUITS ARE
 REQUIRED IN THE KITCHEN PER 220.16.
 PLEASE ADD IN CALCULATIONS.
  
 2} PLEASE PROVIDE A AIC RATING PER 110.9
 & 10.
  
 3} A COUNERTOP RECEPTACLE PER
 210.52(C)(3) MUST BE INSTALLED ON THE
 PENINSULA.
  
 4} PLEASE SEE ARTICLE 11.8.3.5(4)
 REGARDING LOCATION AND TYPE OF SMOKE
 DETECTORS ACCEPTABLE IN THE KITCHEN.
  
 5} THE MASTER BEDROOM, NURSERY AND BOTH
 ROOMS ON THE SECOND LEVEL REQUIRE
 RECEPTACLES TO COMPLY WITH 210.52(A)(1)
 &(2).
  
 6} ELECTRIC PANEL "B" SEEMS TO BE DRAWN
 FREESTANDING. PLEASE SHOW IN CORRECT
 LOCATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW