| Plan Review Notes For Permit 05051060 |
| Permit Number |
05051060 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-09 00:00:00 | ********* UNSAT ******* | | | | | | 1)NOTE: PLEASE SHOW RECEPTS WHICHWILL | | | BE REQUIRED TO MEET 210.52C1-5 FOR | | | KITCHEN COUNTERSPACE ARE. | | | PLEASE ALSO INDICATE AS GFI/GFI | | | PROTECTED PER 210.8A6 | | | | | | 2)NOTE: PLEASE SEE NOTE ON PLANS | | | MENTIONS TO REPLACE RECEPTS TO GFI'S | | | KIT/BATHS. | | | PLEASE SHOW THESE LOCATIONS. | | | 210.52D | | | | | | 3)NOTE: PLEASE SEERAISED SEAL BY ARCH | | | MUST BE CLEAR AND VISABLE WITH ALL | | | INFORMATION REQUIRED ONSAID SEAL PER | | | FAC 61G1-16.003 FS 481.025 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|