Notes
Date Text
2005-07-19 00:00:001) 704.2.1.4 CORRIDOR PARTITIONS,
 SMOKE STOP PARTITIONS, HORIZONTAL EXIT
 PART- ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 TABLE 803.3
 MINIMUM INTERIOR FINISH CLASSIFICATION
  
 R- CLASS C INTERIOR FINISH MATERIALS MAY
 BE USED WITHIN A DWELLING UNIT.
 CLASS C INTERIOR FINISH.FLAMESPREAD
 76-200, SMOKE DEVELOPED 0-450.