2005-08-03 00:00:00IN ELEC FOR REVIEW
 ********* UNSAT 2ND REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE; PLEASE CORRELATE ELECTRICAL SITE
 PLAN WITH ELECTRICAL RISER DIAGRAM'S
 SUBMITTED.
 PLEASE SEE MAINT BLDG ON PLANS INDICATES
 A "PROPOSED MAIN", THIS WAS LOCATED ON
 RISER AND SEEMS TO BE THE NEW MAIN
 REPLACING EXSITNG ATS?, HOWEVER PLEASE
 SEE SITE PLAN FOR MAINT BLDG ALSO
 INDICATES A NEW "PROPOSED ATS" WHICH
 COULD NOT BE LOCATED ON RISER DIAGRAM
 FOR "MAINT BLDG". PLEASE SEE THE ONLY
 NEW PROPOSED ATSSWITCH SHOWN ON RISER
 INDICATES THIS ATS AT PBSO SUB STATION E
 EXTERIOR WALL.
 IF NEW ATS IS AT SUB STATION, PLEASE
 VERIFY IF MDP( NOT ON SITE PLAN)
 CONTAINS A MCB. PLEASE SEE IT WAS NOTED
 ON PREVIOUS REVIEW AND MAIN DISCONNECT
 WILL BE REQUIRED AT PBSO SUB-STATION,
 SHALL BE SERVICE ENTRANCE RATED AND
 GROUPED.225.31,225.34,225.36.
 PLEASE SEE NOTE ON LOWER RIGHT-HAND SIDE
 OF E-1 INDICATES, SHEET FOR INFORMATION
 ONLY" AND "ALL ELECTRICAL WORK SHOWN ON
 E-1 SHALL BE UNDER A SEPARATE PROJECT??
 PLEASE CALRIFY, AS THIS PERMIT
 APPLICATION IS FOR THE NEW WORK AS
 SUBMITTED AND SHOWN ON RISER?
 PLEASE ALSO SEE A NOTE ON E-1 MENTIONS
 FOR A SIGN TO BE PROVIDED FOR GEN
 LOCATION, HOWEVER THIS NOTE MENTIONS GEN
 SHALL BE LOCATED IN AN INTERIOR ROOM
 LOCATED IN THE SW CORNER OF BLDG.??
 PLEASE SEE NEW GEN IS HOWN ON SITE PLAN
 AT MAINT BLDG?
 IS THERE "TWO GEN'S, ONE EXISTING , ONE
 NEW? IF SO PLEASE SEE RISER AND SHOW ALL
 EXISTING AND PROPOSED.
 SITE PLANS SHOW "EXISTING " FEED TO
 MAINT BLDG BEING ABANDONED?
 PLEASE CALRIFY AND CORRELATE. PLEASE SEE
 A TYPED WRITTEN RESPONSE LETTER TO
 COMMENTS WOULD HELP IN ANY
 CLARIFICATIONS.
  
 2)NOTE: PLEASE SEE PREVIOUS NOTE WHICH
 REQUESTED SPECS/MANUFACTURE SHEETS FOR
 ATS AND GEN. PLEASE SEE SHEET FOR ATS
 WERE SUBMITTED, HOWEVER, NONE FOR GEN
 COULD BE LOCATED, ONLY A LTR WHICH
 MENTIONED GEN SHALL BE RE-BUILT.
 PLEASE SEE FUEL TANK SUBMITTIALS ARE NOT
 CLEAR AS ONE SHEET MENTIONS A DIESEL GEN
 AND YET, NEW SHEET MENTIONS NEW GEN TO
 BE GAS?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE RISER SHOWS A NEW
 170KW GEN? SITE PLANS MENTIONS A NEW
 175KW GEN? PLEASE SEE RISER DOES NOT
 INDICATE ANY 175 KW GEN.
 215.5
  
 4)NOTE: PLEASE SEE VALUE FOR SCOPE PF
 WORK WAS NOT INCREASED BY CONTRACTOR. IF
 VALUEIS NOT ADJUSTED BY CONTRACTOR FOR
 ALL WORK AND MATERIALS, A VALUE WILL BE
 APPLIED. PLEASE SEE EVEN IF EQUIPMENT IS
 OWNER SUPPLIED THE PERMIT FEE IS BASED
 ON TOTAL IMPROVEMENT.
 ADIMINSTRATIVE FBC 104.6.5 LOCAL ADMIN
 AMENDMENTS.
  
 5)NOTE: PLEASE SEE ORIGINAL PERMIT
 APPLICATION WAS NOT SUBMITTED BACK WITH
 PACKAGE. PLEASE SEE ONLY A PHOTO-COPY OF
 FRONT WAS SUBMITTED. PLEASE SEE PACKAGE
 MUST CONTAIN SHEET WITH CONTRACTORS
 SIGNATURE AND MUST BE ORIGINAL.
 PLEASE SEE BLDG REVIEW COMMENTS FOR
 THIS.
  
 6)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL. PLEASE SEE THIS ONLY A
 NOTICE GIVEN AT THIS TIME.
 ONE SET OF ELECTRICAL SHEETS ARE BEING
 RETAINED FOR FILE.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 SHEETS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW