| Date |
Text |
| 2005-06-14 00:00:00 | ******** UNSAT ********* |
| | |
| | 1)NOTE; PLEASE CORRELATE PLANS AND RISER |
| | DIAGRAM. |
| | PLEASE SEE E-1 SHOWS EXISTING MAINT BLDG |
| | BEING FED FROM FPL TRANSFORMER AND THIS |
| | FEED IS TO REMAIN. HOWEVER, RISER |
| | DIAGRAM SHOWS THIS MAINT BLDG BEING FED |
| | FROM EXISTING PBSO BLDG?? |
| | PLEASE CORRECT. |
| | |
| | 2)NOTE: PLEASE SEE FEED IS SHOWN ON |
| | RISER COMING INTO MAIN DISCONNECT AND |
| | NOT ATS. PLEASE SEE MEANS OD DISC |
| | REQUIRED FOR FEED FROM GEN LOCATED AT |
| | BLDG, THESE SHALL ALSO BE GROUPED BE |
| | RATED FOR SERVICE ENT EQUIPMENT. |
| | PLEASE SEE 225.31-225.36, SIGNAGE PER |
| | 702.8 |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| | SPECS/CUT SHEETS FOR GENERATOR, ATS. |
| | PLEASE SEE 225.31-225.36 FOR ATS/DISC. |
| | |
| | PLEASE SUBMIT MANUFACTURE CUT/SPECS FOR |
| | SUB-BASE FUEL TANK ALSO FOR MECH/FIRE |
| | REVIEW. 110.3 SHOWING ALL LISTINGS BY A |
| | NRTL. |
| | 215..5 |
| | |
| | 4)NOTE: PLEASE SUPPLY LOAD CALCULATIONS |
| | FOR LOAD TO BE SERVED PER 702.5 |
| | |
| | 5)NOTE: PLEASE SEE VALUE FOR SCOPE OF |
| | WORK IS TO INCLUDE ALL LABOR AND |
| | MATERIALS EVEN IF OWNER SUPPLIED PER FBC |
| | 104.6.5 |
| | THIS WOULD INCLUDE GEN/ATS/TANK ETC. |
| | |
| | 6)NOTE: PLEASE SEE BLDG REVIEW COMMENTS. |
| | PLEASE SEE MISSING LICENSE INFORMATION |
| | REQUIRED ON TITLE BLOCK FOR ENGINEERING |
| | FIRM. |
| | FAC 61G15-23.002, FS 471.023 |
| | THIS COMMENT IS NOT FOR ELECTRICAL ENG |
| | FIRM. |
| | |
| | 7)NOTE: PLEASE SEE ELEVATION ON SURVEY |
| | FOR FLOOD ZONE AND MIN ELEVATION OF |
| | EQUIPMENT. |
| | |
| | PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY HAVE AN AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |