Plan Review Notes
Plan Review Notes For Permit 05051034
Permit Number 05051034
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-14 00:00:00******** UNSAT *********
  
 1)NOTE; PLEASE CORRELATE PLANS AND RISER
 DIAGRAM.
 PLEASE SEE E-1 SHOWS EXISTING MAINT BLDG
 BEING FED FROM FPL TRANSFORMER AND THIS
 FEED IS TO REMAIN. HOWEVER, RISER
 DIAGRAM SHOWS THIS MAINT BLDG BEING FED
 FROM EXISTING PBSO BLDG??
 PLEASE CORRECT.
  
 2)NOTE: PLEASE SEE FEED IS SHOWN ON
 RISER COMING INTO MAIN DISCONNECT AND
 NOT ATS. PLEASE SEE MEANS OD DISC
 REQUIRED FOR FEED FROM GEN LOCATED AT
 BLDG, THESE SHALL ALSO BE GROUPED BE
 RATED FOR SERVICE ENT EQUIPMENT.
 PLEASE SEE 225.31-225.36, SIGNAGE PER
 702.8
 215.5
  
 3)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR GENERATOR, ATS.
 PLEASE SEE 225.31-225.36 FOR ATS/DISC.
  
 PLEASE SUBMIT MANUFACTURE CUT/SPECS FOR
 SUB-BASE FUEL TANK ALSO FOR MECH/FIRE
 REVIEW. 110.3 SHOWING ALL LISTINGS BY A
 NRTL.
 215..5
  
 4)NOTE: PLEASE SUPPLY LOAD CALCULATIONS
 FOR LOAD TO BE SERVED PER 702.5
  
 5)NOTE: PLEASE SEE VALUE FOR SCOPE OF
 WORK IS TO INCLUDE ALL LABOR AND
 MATERIALS EVEN IF OWNER SUPPLIED PER FBC
 104.6.5
 THIS WOULD INCLUDE GEN/ATS/TANK ETC.
  
 6)NOTE: PLEASE SEE BLDG REVIEW COMMENTS.
 PLEASE SEE MISSING LICENSE INFORMATION
 REQUIRED ON TITLE BLOCK FOR ENGINEERING
 FIRM.
 FAC 61G15-23.002, FS 471.023
 THIS COMMENT IS NOT FOR ELECTRICAL ENG
 FIRM.
  
 7)NOTE: PLEASE SEE ELEVATION ON SURVEY
 FOR FLOOD ZONE AND MIN ELEVATION OF
 EQUIPMENT.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  