| 2005-06-17 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05051034 |
| | ADD: 8130 N JOG RD |
| | CONT: HOLT |
| | TEL: (954)755-7200 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1) 471.023 F.S.CERTIFICATE OF |
| | AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ENGINEER |
| | PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING |
| | ENGINEERING SERVICES, SHALL INCLUDE THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER. |
| | ADD THE NUMBER TO EACH SHEET.THIS MAY |
| | BE ADDED BY HAND. |
| | |
| | 2) PROVIDE ADDITIONAL INFORMATION IN |
| | REGUARDS TO ANCHORING OF THE GENERATOR |
| | TO THE SLAB.1606.1.3 ANCHORAGE AGAINST |
| | OVERTURNING, UPLIFT AND SLIDING. |
| | STRUCTURALMEMBERS AND SYSTEMS, AND |
| | COMPONENTS AND CLADDING IN A BUILDING OR |
| | STRUCTURE SHALL BE ANCHORED TO RESIST |
| | WIND-INDUCED OVERTURNING, UPLIFT |
| | AND SLIDING AND TO PROVIDE CONTINUOUS |
| | LOAD PATHS FOR THESE FORCES TO THE |
| | FOUNDATION.WHERE A PORTION OF THE |
| | RESISTANCE TO THESE FORCES IS PROVIDED |
| | BY DEAD LOAD, THE MINIMUM DEAD LOAD |
| | LIKELY TO BE IN PLACE DURING A DESIGN |
| | WIND EVENT SHALL BE USED. |
| | |
| | 3)407.2.3 SPILL CONTROL, DRAINAGE AND |
| | CONTAINMENT |
| | PROVIDE INFORMATION ON THE 350 GALLON |
| | DIESEL FUEL TANK. |
| | 407.2.3.1 GENERAL. ROOMS, BUILDINGS |
| | OR AREAS USED FOR THE STORAGE OR |
| | DISPENSING OF SOLID OR LIQUID |
| | HAZARDOUS MATERIALS SHALL BE PROVIDED |
| | WITH A MEANS TO CONTROL SPILLAGE AND |
| | TO CONTAIN OR DRAIN SPILLAGE AND |
| | FIRE PROTECTION WATER DISCHARGED IN |
| | THE STORAGE AREA.A MEANS TO |
| | CONTROL SPILLAGE SHALL BE PROVIDED |
| | IN OPEN SYSTEMS IN WHICH DISPENSING |
| | IS DONE INTO CONTAINERS EXCEEDING 1 |
| | GAL (3.79 L) CAPACITY, OR USED IN |
| | OPEN CONTAINERS OR SYSTEMS EXCEEDING |
| | 5 GAL (18.9 L) CAPACITY, OR IN |
| | CLOSED SYSTEMS EXCEEDING 55 GAL |
| | (208.2 L) CAPACITY. |
| | BUILDING PLAN REVIEW |