2005-09-10 00:00:00REDLINED PLANS,
 PANEL "C" SHALL NOT BE LOCATES IN A
 "STORAGE RM".
 240.24D,110.26,408.7
 THIS RM AS SHOWN IS ONLY TO BE A
 ELECTRICAL / EMCH RM OR PANEL IS TO BE
 MOVED.