Plan Review Notes
Plan Review Notes For Permit 05051005
Permit Number 05051005
Review Stop B
Sequence Number 2
Notes
Date Text
2005-07-22 00:00:00BUILDING PLAN REVIEW
 PERMIT:05051005
 ADD:743 BISCAYNE DR.
 CONT:STEPHEN ROY
 TEL: (561)248-9516
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION:DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 3) WHICH ONE OF THE DECK WILL BE
 CONCRETE? ONE OF THE PRODUCT APPROVAL
 SUBMITTED REFERS TO A CONCRETE DECK.
 ALSO NONE OF THE PRODUCT APPROVALS HAVE
 THE STATE COVER SHEETS. ALL PRODUCTS
 SUBMITTED NEEDS THE MATCHING CURRENT
 STATE COVER SHEET. I AM SUPPLYING YOU
 WITH AN EXAMPLE OF THE STATE COVER SHEET
 WITH ONE OF THE PRODUCT YOU SUBMITTED,
 SO YOU CAN SEE WHAT I AM SPEAKING OF.
  
 4) THE PRODUCT APPROVALS SUBMITTED FOR
 THE METAL ROOF NEEDS A STATE APROVAL
 REPORT ALONG WITH THE STATE COVER
 SHEETS. THE MANUFACTURE INFORMATION
 ALONE IS NOT ACCEPTABLE. ALSO PLEASE SEE
 FBC.1507.6.2 DECK SLOPE. METAL ROOF
 SHINGLES SHALL NOT BE INSTALLED ON ROOF
 SLOPES BELOW 3:12.
 1507.6.3 UNDERLAYMENT. UNDERLAYMENT
 SHALL CONFORM WITH ASTM D 226, TYPE
 I.
 5) IS THE CARRAGE HOUSE GETTING A NEW
 FLAT ROOF? OR IS THE ROOF EXISTING?
 PLEASE CLARIFY. IF IT IS A NEW ROOF,
 SUPPLY PRODUCT APPROVAL FOR THE FLAT
 ROOF.WHEN SUBMITTING PRODUCT APPROVALS
 FOR THE FLAT ROOF, PLEASE KNOW THAT
 SYSTEMS THAT STATES GENERAL LIMITATIONS
 #9 WITH -PSF LESS THAT -89PSF IS NOT
 ACCEPTABLE.
  
 6) FBC 1606.2.5.GENERAL LIMITATION
 #9 PROHIBITS RATIONAL ANALYSIS OR
 EXTRAPOLATION TO ENHANCE THE UPLIFT
 PRESSURE AT PERIMETER AND CORNER AREAS
 BY REDUCING THE FASTENER SPACING IN
 THESE AREAS.EITHER SELECT AN
 ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL)
 THAT DOES NOT CITE GENERAL LIMITATION
 #9.ALTERNATIVELY IF THE SELECTED
 SYSTEM DOES CITE GENERAL LIMITATION #9,
 IT MUST HAVE A MAXIMUM DESIGN PRESSURE
 THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3
 (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT
 OF 30 FEET OR LESS).
  
 7) ON SHEET A.5, IF DOOR 'E' WILL BE
 USED PLEASE SUPLY PRODUCT APPROVAL FOR
 THAT DOOR OR YOU MAY APPLY FOR LOCAL
 PRODUCT APPROVAL. SEE APPLICATION IN
 PACKAGE.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved