| Notes |
| Date |
Text |
| 2005-05-31 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} INDICATE THE LOCATION OF THE SERVICE | | | SO THAT DISCONNECT REQUIREMENTS CON BE | | | REVIEWED. | | | | | | 2} SHOW LOCATION OF THE PANEL SERVING | | | THE REC ROOM, DISCONNECTING MEANS AND | | | GROUNDING. | | | | | | 3} PLEASE PUT ROOM DESIGNATIONS ON THE | | | ELECTRICAL FLOOR PLANS. | | | | | | 4} THE PANEL DESIGNATION ON THE RISER | | | AND PANEL SCHEDULE DO NOT CCORRELATE. | | | "C" & "G". | | | | | | 5} SEE 210.52(C)(2) FOR ISLAND | | | RECEPTACLE REQUIREMENTS.INDICATE | | | COMPLIANCE ON PLANS. | | | | | | 6} REC ROOM KITCHEN COUNTERTOP | | | RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(C)(1). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|