 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE LOCATION OF THE SERVICE
 SO THAT DISCONNECT REQUIREMENTS CON BE
 REVIEWED.
  
 2} SHOW LOCATION OF THE PANEL SERVING
 THE REC ROOM, DISCONNECTING MEANS AND
 GROUNDING.
  
 3} PLEASE PUT ROOM DESIGNATIONS ON THE
 ELECTRICAL FLOOR PLANS.
  
 4} THE PANEL DESIGNATION ON THE RISER
 AND PANEL SCHEDULE DO NOT CCORRELATE.
 "C" & "G".
  
 5} SEE 210.52(C)(2) FOR ISLAND
 RECEPTACLE REQUIREMENTS.INDICATE
 COMPLIANCE ON PLANS.
  
 6} REC ROOM KITCHEN COUNTERTOP
 RECEPTACLE SPACING MUST COMPLY WITH
 210.52(C)(1).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW