| Notes |
| Date |
Text |
| 2005-05-26 00:00:00 | | | | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | 1} INDICATE THE LOCATION OF PANEL | | | "B"&"C". | | | | | | 2} INDICATE LOCATION OF OVERCURRENT | | | PROTECTION FOR PANELS "A" & "B". | | | | | | 3} THE OCP FOR CIRCUITS 16,17 PANEL "A", | | | 12,13,14,15 PANEL "B" IS TOO LARGE FOR | | | THE CONDUCTORS PER 210.16. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|