| Notes |
| Date |
Text |
| 2006-02-10 00:00:00 | | | | THE GROUNDING ELECTRODE SYSTEM DOES NOT | | | COMPLY WITH 250.52(A)(3). THE PERMITED | | | PLANS WITH THE ARCHITECTS SEAL INDICATED | | | COMPLIANCE, AND FOOTER STEEL WAS | | | AVAILABLE PER 250.50 AS THIS IS A NEW | | | RESIDENCE. RESUBMIT INDICATING | | | COMPLIANCE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|