Plan Review Notes
Plan Review Notes For Permit 05050970
Permit Number 05050970
Review Stop E
Sequence Number 3
Notes
Date Text
2005-07-29 00:00:00******** NOTE REDLINED ********
  
 1)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 REVISE ANY CIRCUTING/LABELING OF GFI
 CIRCUITS/RECEPTS.
  