| Plan Review Notes For Permit 05050970 |
| Permit Number |
05050970 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-07-29 00:00:00 | ******** NOTE REDLINED ******** | | | | | | 1)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR | | | KITCHENS IN OTHER THAN DWELLING UNITS | | | WHICH REQUIRES ALL 15- AND 20-AMPERE, | | | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE | | | KITCHENS TO BE GFCI PROTECTED. THIS | | | REQUIREMENT APPLIES TO EACH AND EVERY | | | 15- AND 20-AMPERE, 125-VOLT KITCHEN | | | RECEPTACLE, WHETHER OR NOT THE | | | RECEPTACLE SERVES COUNTERTOP APPLIANCES. | | | | | | REVISE ANY CIRCUTING/LABELING OF GFI | | | CIRCUITS/RECEPTS. | | | | | 2005-07-28 00:00:00 | IN ELEC FOR REVIEW |
|