Plan Review Notes
Plan Review Notes For Permit 05050970
Permit Number 05050970
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-08 00:00:00********** UNSAT **********
  
 1)NOTE: PLEASE SEE MIN CLEARENCE
 REQUIRED IN ELECTRICAL ROOM. 110.26
  
 2)NOTE: PLEASE PLACE NOTE ON ELECTRICAL
 PLANS FOR RATING OF IT ROOM,
 DISCONNECTING MEANS AND OR/ FIRE DAMPERS
 PER 645.10,645.2
  
 3)NOTE: PLEASE ALSO SEE 645.11 FOR
 DISCONNECTING MEANS.
  
 4)NOTE: PLEASE SEE PANEL "L" WHICH IS
 REQUIRED TO BE A MCB PANEL. 408.16
 PLEASE CLARIFY. PLEASE ALSO SEE WITH THE
 AMOUNT OF WORK BEING DONE TO THIS SPACE
 A MCB WILL BE REQUIRED TO BE INSTALLED
 IF NOT PRESENT AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  