| Date |
Text |
| 2005-07-01 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | |
| | |
| | 1. SHT A-2.03 KITCHEN IN COMMUNITY ROOM |
| | TO BE ACCESSIBLE. PLEASE PROVIDE A |
| | DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.24 AND ALL SUBSECTIONS. |
| | 2. SHTS A2.07, A4.70 THRU A4.77, P2.02.1 |
| | AND P2.06 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106, & 1107 AND ALL |
| | SUBSECTIONS. SHOW THE LOCATION OF ALL |
| | PRIMARY AND SECONDARY ROOF DRAINS AS |
| | WELL AS ANY SCUPPERS. SUBMIT A DETAIL |
| | FOR SCUPPERS IF USED INDICATING THE |
| | HEIGHT AND WIDTH. SHOW THE SQUARE |
| | FOOTAGE OF ALL AREAS WITH 1/2 AREA OF |
| | ALL VERTICAL WALLS INCLUDING PARAPETS, |
| | PLUS THE AREAS OF ALL ROOFS AREAS THAT |
| | DRAIN DOWN TO ROOF AREAS FROM ABOVE IN |
| | THE CALCULATIONS. |
| | 3. SHTS A4.00 THRU A4.02, A4.20 THRU |
| | A4.25, AND A4.30 THRU A4.65 SHOW |
| | COMPLIANCE WITH FHA-98 DESIGN MANUAL |
| | REQUIREMENTS 1 THRU 7. |
| | 4. SHT A4.25 MENS AND WOMENS TOILET |
| | ROOMS TO BE ACCESSIBLE. SHOW COMPLIANCE |
| | WITH SECTIONS 11-4.16, 11-4.18, 11-4.19, |
| | AND 11-4.22 AND ALL SUBSECTIONS. |
| | 5. SHT A4.27 SUBMIT A DETAIL FOR THE |
| | DRINKING FOUNTAIN SHOWING COMPLIANCE |
| | WITH SECTION 11-4.15 AND ALL SUBSECTIONS |
| | AS WELL AS 11-4.1.3(10)(A) PROVISIONS |
| | FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | 6. SHT A9.08 ROOM FINISH SCHEDULE. MENS |
| | AND WOMENS TOILET ROOMS STATE, "SEE |
| | INTERIOR DESIGN DRAWINGS FOR LOCATION OF |
| | MATERIALS". THESE WERE NOT INDICATED ON |
| | THE DRAWING LIST. PLEASE INDICATE WHERE |
| | THE INTERIOR DESIGN DRAWINGS ARE |
| | LOCATED. SECTION 104.2.1. |
| | 7. P2.00UG P&T LINE. THE DISCHARGE PIPE |
| | SHALL NOT HAVE ANY TRAPPED SECTIONS. |
| | SECTION 504.7.1 |
| | 8. SHT P2.00UG UNITS 103 AND 106 NO |
| | PIPING SHOWN TO RISERS (SANT. RELIEF, |
| | AND COND.) - IDENTIFY ALL SANITARY |
| | RISERS. SECTION 104.2.1. |
| | 10. P2.001 STORM AND OVERFLOW RISERS AT |
| | COL. LINES A/3 & A/5 NOT SHOWN ON FLOOR |
| | PLAN. SECTION 104.2.1. |
| | 11. SHT P200 SANT. PIPING DOES NOT |
| | REFLECT THE FLOOR PLAN. SECTION 104.2.1. |
| | 12. SHT P2.01 PIPING SHOWN DOES NOT |
| | REFLECT THE FIXTURE LAYOUT. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | 13. SHT P2.05 DWV PIPING NOT SHOWN. SHOW |
| | PIPING TO REFLECT THE SANT. RISER |
| | DIAGRAMS. SECTIONS 104.2.1 & 104.3.1.1. |
| | 14. SHT P2.05 FLOOR PLAN SHOWS OFFSET IN |
| | SANT. RISERS S/11 & S/16, (UNITS 611 AND |
| | 609), THAT ARE NOT SHOWN ON THE SANT. |
| | RISER DIAGRAMS. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 15. SHT P3.01 WATER LINES (PP & CP ARE |
| | UNCLEAR AS TO THEIR INTENT IN THE |
| | CEILING. IS THE POOL/IRRIGATION WATER, |
| | LOFT WATER AND WR/11 ON PP OR CITY |
| | PRESSURE? THE WATER LINES ARE NOT |
| | SEPARATED FROM EACH OTHER FAR ENOUGH TO |
| | IDENTIFY WHICH LINE THE SUPPLY LINES ARE |
| | CONNECTED TO. |
| | 16. SHT P3.02 ALL WATER ISOMETRICS, |
| | WATER HAMMER ARRESTORS ARE REQUIRED AT |
| | THE DISH WASHER, AND THE ICE MAKER IN |
| | THE REF. SECTION 604.9. |
| | 17. SHT P3.05 DECK DRAINS SHOW 2000SF, |
| | BUT OVERFLOW DRAINS SHOW 1660SF. - ALSO |
| | DECK DRAINS SHOW 1270SF BUT OVERFLOW |
| | DRAINS SHOW 890SF. PLEASE CLARIFY. |
| | SECTION 1107 & TABLE 1106.3. |
| | 18. SHT P3.05 UNABLE TO LOCATE ROOF |
| | DRAINS AND OVERFLOW DRAINS ON RISER WITH |
| | 2505 SF ON THE 2ND FLOOR POOL DECK FLOOR |
| | PLAN. PLEASE INDICATE WHERE THESE DRAINS |
| | ARE LOCATED. SHTS P2.01.1 & P2.01 |
| | INDICATE 3 RISERS. SHT P3.05 SHOWS 4 |
| | RISERS. PLEASE CLARIFY. SECTION 104.2.1. |
| | 19. SUBMIT A BUILDING STORM DRAIN |
| | ISOMETRIC FOR PRIMARY AND SECONDARY |
| | (OVERFLOW) SYSTEMS. SHOW ALL PIPE SIZES, |
| | LOCATION OF RISER CONNECTIONS, & SQUARE |
| | FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. |
| | SECTION 104.3.1.1. |
| | 20. SUBMIT A CONDENSATE BUILDING DRAIN |
| | ISOMETRIC, SHOWING ALL PIPE SIZES AND |
| | RISER CONNECTIONS. SECTION 104.3.1.1. |
| | 21. SUBMIT AN EMERGENCY PAN DRAIN |
| | BUILDING DRAIN ISOMETRIC. SHOW ALL PIPE |
| | SIZES, AND RISER CONNECTIONS. INDICATE |
| | PIPING MATERIAL. SECTION 104.3.1.1. |
| | 22. SHT C-2 IRRIGATION REQUIRES AN RPZ |
| | BACKFLOW. SECTION 608.13.2. - SEPARATE |
| | PLANS AND PERMIT REQUIRED FOR |
| | IRRIGATION. |
| | 23. PLANS DO NOT APPEAR TO BE 100% |
| | COMPLETE AT THIS REVIEW. MORE COMMENTS |
| | MAY BE FORTHCOMING AFER PLANS ARE |
| | RESUBMITTED. |
| | |