Plan Review Notes
Plan Review Notes For Permit 05050638
Permit Number 05050638
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
  
 1. SHT A-2.03 KITCHEN IN COMMUNITY ROOM
 TO BE ACCESSIBLE. PLEASE PROVIDE A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 AND ALL SUBSECTIONS.
 2. SHTS A2.07, A4.70 THRU A4.77, P2.02.1
 AND P2.06 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, & 1107 AND ALL
 SUBSECTIONS. SHOW THE LOCATION OF ALL
 PRIMARY AND SECONDARY ROOF DRAINS AS
 WELL AS ANY SCUPPERS. SUBMIT A DETAIL
 FOR SCUPPERS IF USED INDICATING THE
 HEIGHT AND WIDTH. SHOW THE SQUARE
 FOOTAGE OF ALL AREAS WITH 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS,
 PLUS THE AREAS OF ALL ROOFS AREAS THAT
 DRAIN DOWN TO ROOF AREAS FROM ABOVE IN
 THE CALCULATIONS.
 3. SHTS A4.00 THRU A4.02, A4.20 THRU
 A4.25, AND A4.30 THRU A4.65 SHOW
 COMPLIANCE WITH FHA-98 DESIGN MANUAL
 REQUIREMENTS 1 THRU 7.
 4. SHT A4.25 MENS AND WOMENS TOILET
 ROOMS TO BE ACCESSIBLE. SHOW COMPLIANCE
 WITH SECTIONS 11-4.16, 11-4.18, 11-4.19,
 AND 11-4.22 AND ALL SUBSECTIONS.
 5. SHT A4.27 SUBMIT A DETAIL FOR THE
 DRINKING FOUNTAIN SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 AS WELL AS 11-4.1.3(10)(A) PROVISIONS
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 6. SHT A9.08 ROOM FINISH SCHEDULE. MENS
 AND WOMENS TOILET ROOMS STATE, "SEE
 INTERIOR DESIGN DRAWINGS FOR LOCATION OF
 MATERIALS". THESE WERE NOT INDICATED ON
 THE DRAWING LIST. PLEASE INDICATE WHERE
 THE INTERIOR DESIGN DRAWINGS ARE
 LOCATED. SECTION 104.2.1.
 7. P2.00UG P&T LINE. THE DISCHARGE PIPE
 SHALL NOT HAVE ANY TRAPPED SECTIONS.
 SECTION 504.7.1
 8. SHT P2.00UG UNITS 103 AND 106 NO
 PIPING SHOWN TO RISERS (SANT. RELIEF,
 AND COND.) - IDENTIFY ALL SANITARY
 RISERS. SECTION 104.2.1.
 10. P2.001 STORM AND OVERFLOW RISERS AT
 COL. LINES A/3 & A/5 NOT SHOWN ON FLOOR
 PLAN. SECTION 104.2.1.
 11. SHT P200 SANT. PIPING DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 104.2.1.
 12. SHT P2.01 PIPING SHOWN DOES NOT
 REFLECT THE FIXTURE LAYOUT. PLEASE
 CLARIFY. SECTION 104.2.1.
 13. SHT P2.05 DWV PIPING NOT SHOWN. SHOW
 PIPING TO REFLECT THE SANT. RISER
 DIAGRAMS. SECTIONS 104.2.1 & 104.3.1.1.
 14. SHT P2.05 FLOOR PLAN SHOWS OFFSET IN
 SANT. RISERS S/11 & S/16, (UNITS 611 AND
 609), THAT ARE NOT SHOWN ON THE SANT.
 RISER DIAGRAMS. PLEASE CLARIFY. SECTION
 104.2.1.
 15. SHT P3.01 WATER LINES (PP & CP ARE
 UNCLEAR AS TO THEIR INTENT IN THE
 CEILING. IS THE POOL/IRRIGATION WATER,
 LOFT WATER AND WR/11 ON PP OR CITY
 PRESSURE? THE WATER LINES ARE NOT
 SEPARATED FROM EACH OTHER FAR ENOUGH TO
 IDENTIFY WHICH LINE THE SUPPLY LINES ARE
 CONNECTED TO.
 16. SHT P3.02 ALL WATER ISOMETRICS,
 WATER HAMMER ARRESTORS ARE REQUIRED AT
 THE DISH WASHER, AND THE ICE MAKER IN
 THE REF. SECTION 604.9.
 17. SHT P3.05 DECK DRAINS SHOW 2000SF,
 BUT OVERFLOW DRAINS SHOW 1660SF. - ALSO
 DECK DRAINS SHOW 1270SF BUT OVERFLOW
 DRAINS SHOW 890SF. PLEASE CLARIFY.
 SECTION 1107 & TABLE 1106.3.
 18. SHT P3.05 UNABLE TO LOCATE ROOF
 DRAINS AND OVERFLOW DRAINS ON RISER WITH
 2505 SF ON THE 2ND FLOOR POOL DECK FLOOR
 PLAN. PLEASE INDICATE WHERE THESE DRAINS
 ARE LOCATED. SHTS P2.01.1 & P2.01
 INDICATE 3 RISERS. SHT P3.05 SHOWS 4
 RISERS. PLEASE CLARIFY. SECTION 104.2.1.
 19. SUBMIT A BUILDING STORM DRAIN
 ISOMETRIC FOR PRIMARY AND SECONDARY
 (OVERFLOW) SYSTEMS. SHOW ALL PIPE SIZES,
 LOCATION OF RISER CONNECTIONS, & SQUARE
 FOOTAGE AS IT ACCUMULATES IN THE SYSTEM.
 SECTION 104.3.1.1.
 20. SUBMIT A CONDENSATE BUILDING DRAIN
 ISOMETRIC, SHOWING ALL PIPE SIZES AND
 RISER CONNECTIONS. SECTION 104.3.1.1.
 21. SUBMIT AN EMERGENCY PAN DRAIN
 BUILDING DRAIN ISOMETRIC. SHOW ALL PIPE
 SIZES, AND RISER CONNECTIONS. INDICATE
 PIPING MATERIAL. SECTION 104.3.1.1.
 22. SHT C-2 IRRIGATION REQUIRES AN RPZ
 BACKFLOW. SECTION 608.13.2. - SEPARATE
 PLANS AND PERMIT REQUIRED FOR
 IRRIGATION.
 23. PLANS DO NOT APPEAR TO BE 100%
 COMPLETE AT THIS REVIEW. MORE COMMENTS
 MAY BE FORTHCOMING AFER PLANS ARE
 RESUBMITTED.
  
 REVIEW BY KEN STEVENS