Plan Review Notes
Plan Review Notes For Permit 05050638
Permit Number 05050638
Review Stop M
Sequence Number 1
Notes
Date Text
2005-07-07 00:00:00DENIED:
 1.PLAN SHEET A1.03 & A1.04 ARE MISSING
 FROM THE SUBMITTED PLANS.PLEASE
 PROVIDE ABBREVAIATION, DATA SHEET.
  
 2.PLAN SHEET M0.02, THE FAN SCHEDULE
 INDICATES EF-2, DRYER BOOSTER FANS.
 THIS APPLICATION WILL HAVE TO BE
 SUBMITTED TO THE BUILDING OFFICAL UNDER
 "ALTERNATE MATERIALS AND METHODS" AS
 SPECIFIED IN THE AMENDMENTS TO THE 2001
 FBC 103.7.1.PLEASE PROVIDE BOOSTER FAN
 SUBMITTAL AND A LETTER FROM THE ENGINEER
 OF THE DRYER MANUFACTURER INDICATING THE
 APPLICATION OF THE DRYER BOOSTER FAN
 WILL NOT VOID THE WARRANTY OF THE DRYER.
 PLEASE NOTE, SHOULD THE BOOSTER FAN
 FAIL, THE DRYER DUCT IS NO LONGER IN
 COMPLIANCE WITH 2001 FBC(M)504.6.
  
 3.PLAN SHEET M0.02, FAN SCHEDULE
 INDICATES THE GARAGE EXHAUST FANS WILL
 NOT BE INTERLOCKED TO THE EMERGENCY
 POWER.DURING A POWER OUTAGE HOW
 WILL THE GARAGE MAINTAIN THE REQUIREMENT
 OF 6 AIR CHANGES PER HOUR FOR EACH LEVEL
 PER 2001 FBC 411.4.
  
 4.PLAN SHEET M2.00.1 INDICATES
 NUMEROUS EXHAUST & AIR MAKE-UP INTO &
 FROM THE GARAGE.PLEASE EXPLAIN
 RATIONALE AS TO HOW THE AIR EXCHANGE
 WILL TAKE PLACE WHEN THE FANS IN THE
 GARAGE DO NOT RUN CONTINUOUSLY.
  
 5.PER 2001 FBC(M)501.3, EVERY
 MECHANICAL EXHAUST SHALL BE DISCHARGED
 OUTDOORS AT A POINT WHERE IT CANNOT BE
 DRAWN IN BY THE VENTILATING SYSTEM.
  
 6.PLAN SHEET M2.00.2, PLEASE CLARIFY
 THE ELEVATION OF THE EXHAUST FROM THE
 GENERATOR MUFFLER.PROVIDE DISTANCE TO
 THE PROPERTY LINE.EXHUAST SHALL NOT
 TERMINATE ONTO A WALKWAY 2001
 FBC(M)401.5.2.
  
 7.PLANS APPEAR TO INDICATE A "FREE
 RETURN" BACK TO THE AHU. THE DOOR
 INDICATES LOUVERED DOOR TO THE AHU
 CLOSET.PLEASE NOTE, THE DOOR TO THE
 AHU CLOSET SHALL COMPLY WITH 2001 FBC(M)
 602.2.1.
  
 8.PLEASE INDICATE LOCATION OF RETURN
 AIR I.E., BOTTOM OR SIDE OF THE AHU. PER
 2001 FBC(M)307.2.3, AUXILIARY DRAIN PAN
 WITH OVERFLOW PROTECTION REQUIRED.
  
 9.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS FOR ALL AREAS, RESIDENTIAL
 AND COMMON IN ACCORDANCE WITH 2001
 FBC(M) CHAPTER 4.
  
 10. FAN SHUTDOWN WITH NOTIFICATION
 REQUIRED FOR SYTSEMS WITH THE DESIGN
 CAPACITY OF GREATER THAN 2,000 CFM PER
 2001 FBC(M)606.2.1.
  
 PLEASE NOTE, RESPONSE TO COMMENTS MAY
 GENERATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  