Plan Review Notes
Plan Review Notes For Permit 05050638
Permit Number 05050638
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-06-20 00:00:001. WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING, AND AFTER
 CONSTRUCTION.
  
 2. A KNOX-BOX WILL BE REQUIRED.
  
 3. KNOX-BOX LOCKING CAPS WILL BE
 REQUIRED ON FIRE DEPARTMENT CONNECTION.
 (FDC)
  
 4. ON PAGE LS2.01 INDICATES A ONE
 HOUR FIRE SEPARATION FOR THE GARAGE
 RESIDENTIAL PORTION. A TWO HOUR FIRE
 SEPARATION WILL BE REQUIRED BETWEEN
 THE GARAGE AND RESIDENTIAL PORTION.
  
 5. SEVERAL DOORS APPEAR TO SWING TOO
 FAR INTO THE CORRIDORS ON THE LIFE
 SAFETY PLAN.
  
 6. PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 7. FIRE WALL RATINGS ON LIFE SAFETY
 PLANS ARE DIFFICULT TO READ IN SOME
 LOCALES.
  
 8. PLEASE VERIFY DOOR SWINGS FROM POOL
 DECK.
  
 9. PLEASE EXPLAIN STORAGE LOCKERS IN
 EXIT ACCESS CORRIDORS.
  
 10. PLEASE CLEARLY INDICATE EXIT
 DISCHARGE LOCATIONS AT THE GROUND
 LEVEL.
  
 11. SIGNS ARE REQUIRED IN STAIRWELLS
 INDICATING STAIR NUMBER, STAIR TERMINUS
 TOP AND BOTTOM, FLOOR NUMBER ETC.
  
 12. BUILDING WILL BE REQUIRED TO BE
 COMPLETELY FIRE SPRINKLER PROTECTED
 IN ACCORDANCE WITH FS 553.895 (2).
  
 13. THE REQUIRED FIRE ALARM SYSTEM
 SHALL BE MONITORED BY A LICENSED UL
 LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 14. ELECTRIC POWERED SMOKE DETECTORS
 ARE REQUIRED ON EVERY LEVEL OF THE
 RESIDENTIAL PORTIONS.
  
 15. PLEASE PROVIDE DETAILS ON ELEVATOR
 LOBBY SEPARATION DOORS.
  
 16. STAIRS SHALL ILLUSTRATE STANDPIPE
 CONECTIONS ON EACH FLOOR.
  
 17. PLEASE PROVIDE MORE DETAILS FOR
 CANOPY SHOWN A4.26.
  
 18. HOW IS STAIR # 3 GOING TO BE
 IDENTIFIED AND ILLUMINATED TO DIRECT
 PERSONS TO IT.
  
 19. PLEASE INDICATE WHICH ELEVATOR
 IS STRETCHER ACCESSIBLE. HOW WILL IT
 BE IDENTIFIED.
  
 20. WARNING SIGNS REQUIRED AT ELEVATORS
 TO WARN PERSONS NOT TO USE THEM DURING
 FIRES.
  
 21. TACTILE SIGNAGE REQUIRED AT EXIT
 DOORS.
  
 22. TRASH CHUTE TO COMPLY WITH NFPA 82.
  
 23. WORK IS TO COMPLY WITH NFPA 241
 WHILE THE BUILDING IS UNDER
 CONSTRUCTION.
  
 24. STAIRS POSSIBLY SHOWN ON PAGE
 A4.76 WITHOUT HANDRAILS ON BOTH
 SIDES.
  
 25. SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM
 SYSTEM.
  
 26. STEPS NOTED ON PAGE A7.16. HANDRAILS
 PRESENT?
  
 27. DECORATIVE LIGHT FIXTURE ON PAGE
 A7.07 APPEARS OVER THE PROPERTY LINE.
  
 28. FIRE PROTECTION FOR COOLING TOWER
 TO COMPLY WITH NFPA 214.
  
 29. TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE STORIES
 OR THIRTY FEET IN HEIGHT.
  
 30. STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 31. EXIT SIGNS ON PAGE E2.01.1 ARE
 LEADING PERSONS INTO THE GARAGE. THIS
 DOES NOT APPEAR TO BE CORRECT.
  
 32. ARE THERE EMERGENCY LIGHTS IN
 COMMUNITY ROOM AND EXERCISE ROOMS.
  
 33. EXIT SIGN SHALL NOT EXCEED 100 FEET.
  
 34. THE FIRE DEPARTMENT CONECTION SHALL
 NOT EXCEED 150 FEET TO A FIRE HYDRANT.
  
 MIKE CARSILLO, FIRE MARSHAL
 835-2910