| 2005-06-20 00:00:00 | 1. WET FIRE HYDRANTS ARE REQUIRED |
| | PRIOR TO, DURING, AND AFTER |
| | CONSTRUCTION. |
| | |
| | 2. A KNOX-BOX WILL BE REQUIRED. |
| | |
| | 3. KNOX-BOX LOCKING CAPS WILL BE |
| | REQUIRED ON FIRE DEPARTMENT CONNECTION. |
| | (FDC) |
| | |
| | 4. ON PAGE LS2.01 INDICATES A ONE |
| | HOUR FIRE SEPARATION FOR THE GARAGE |
| | RESIDENTIAL PORTION. A TWO HOUR FIRE |
| | SEPARATION WILL BE REQUIRED BETWEEN |
| | THE GARAGE AND RESIDENTIAL PORTION. |
| | |
| | 5. SEVERAL DOORS APPEAR TO SWING TOO |
| | FAR INTO THE CORRIDORS ON THE LIFE |
| | SAFETY PLAN. |
| | |
| | 6. PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENTS FOR ALL HANDRAILS AND |
| | GUARDRAILS. |
| | |
| | 7. FIRE WALL RATINGS ON LIFE SAFETY |
| | PLANS ARE DIFFICULT TO READ IN SOME |
| | LOCALES. |
| | |
| | 8. PLEASE VERIFY DOOR SWINGS FROM POOL |
| | DECK. |
| | |
| | 9. PLEASE EXPLAIN STORAGE LOCKERS IN |
| | EXIT ACCESS CORRIDORS. |
| | |
| | 10. PLEASE CLEARLY INDICATE EXIT |
| | DISCHARGE LOCATIONS AT THE GROUND |
| | LEVEL. |
| | |
| | 11. SIGNS ARE REQUIRED IN STAIRWELLS |
| | INDICATING STAIR NUMBER, STAIR TERMINUS |
| | TOP AND BOTTOM, FLOOR NUMBER ETC. |
| | |
| | 12. BUILDING WILL BE REQUIRED TO BE |
| | COMPLETELY FIRE SPRINKLER PROTECTED |
| | IN ACCORDANCE WITH FS 553.895 (2). |
| | |
| | 13. THE REQUIRED FIRE ALARM SYSTEM |
| | SHALL BE MONITORED BY A LICENSED UL |
| | LISTED CENTRAL STATION APPROVED FOR |
| | CENTRAL STATION SERVICE. |
| | |
| | 14. ELECTRIC POWERED SMOKE DETECTORS |
| | ARE REQUIRED ON EVERY LEVEL OF THE |
| | RESIDENTIAL PORTIONS. |
| | |
| | 15. PLEASE PROVIDE DETAILS ON ELEVATOR |
| | LOBBY SEPARATION DOORS. |
| | |
| | 16. STAIRS SHALL ILLUSTRATE STANDPIPE |
| | CONECTIONS ON EACH FLOOR. |
| | |
| | 17. PLEASE PROVIDE MORE DETAILS FOR |
| | CANOPY SHOWN A4.26. |
| | |
| | 18. HOW IS STAIR # 3 GOING TO BE |
| | IDENTIFIED AND ILLUMINATED TO DIRECT |
| | PERSONS TO IT. |
| | |
| | 19. PLEASE INDICATE WHICH ELEVATOR |
| | IS STRETCHER ACCESSIBLE. HOW WILL IT |
| | BE IDENTIFIED. |
| | |
| | 20. WARNING SIGNS REQUIRED AT ELEVATORS |
| | TO WARN PERSONS NOT TO USE THEM DURING |
| | FIRES. |
| | |
| | 21. TACTILE SIGNAGE REQUIRED AT EXIT |
| | DOORS. |
| | |
| | 22. TRASH CHUTE TO COMPLY WITH NFPA 82. |
| | |
| | 23. WORK IS TO COMPLY WITH NFPA 241 |
| | WHILE THE BUILDING IS UNDER |
| | CONSTRUCTION. |
| | |
| | 24. STAIRS POSSIBLY SHOWN ON PAGE |
| | A4.76 WITHOUT HANDRAILS ON BOTH |
| | SIDES. |
| | |
| | 25. SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE SPRINKLER AND FIRE ALARM |
| | SYSTEM. |
| | |
| | 26. STEPS NOTED ON PAGE A7.16. HANDRAILS |
| | PRESENT? |
| | |
| | 27. DECORATIVE LIGHT FIXTURE ON PAGE |
| | A7.07 APPEARS OVER THE PROPERTY LINE. |
| | |
| | 28. FIRE PROTECTION FOR COOLING TOWER |
| | TO COMPLY WITH NFPA 214. |
| | |
| | 29. TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN THE BUILDING REACHES THREE STORIES |
| | OR THIRTY FEET IN HEIGHT. |
| | |
| | 30. STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 31. EXIT SIGNS ON PAGE E2.01.1 ARE |
| | LEADING PERSONS INTO THE GARAGE. THIS |
| | DOES NOT APPEAR TO BE CORRECT. |
| | |
| | 32. ARE THERE EMERGENCY LIGHTS IN |
| | COMMUNITY ROOM AND EXERCISE ROOMS. |
| | |
| | 33. EXIT SIGN SHALL NOT EXCEED 100 FEET. |
| | |
| | 34. THE FIRE DEPARTMENT CONECTION SHALL |
| | NOT EXCEED 150 FEET TO A FIRE HYDRANT. |
| | |
| | MIKE CARSILLO, FIRE MARSHAL |